46/128 Product information
S-0-0390
P-0-1300
S-0-0095
F2013
D300
D300: oil level of
tank too high
F2013
D301
D301: oil level of tank
too low
F2013
D302
D302: particle
content S too high
F2013
D303
D303: particle
content M too high
F2013
D304
D304: particle
content L too high
F2013
D305
D305: particle
content XL too high
F2013
D306
D306: filter clogging
too high
F2013
D307
D307: oil
temperature too high
F2013
D308
D308: oil
temperature too low
F2013
D309
D309: oxygen
content too high
F2013
D310
D310: relative
humidity too high
F2013
D318
D318: leakage very
high
Bosch Rexroth AG, CytroBox, RE 51057-B/11.19
Table 38: Error
Cause
The monitoring of the oil level
indicates an alarm.
P-0-1291 > P-0-1389[74]
The monitoring of the oil level
indicates an alarm.
P-0-1291 < P-0-1389[73]
The monitoring of the particle
concentration indicates an
alarm.
P-0-1424 > P-0-1389[65]
The monitoring of the particle
concentration indicates an
alarm.
P-0-1425 > P-0-1389[66]
The monitoring of the particle
concentration indicates an
alarm.
P-0-1426 > P-0-1389[67]
The monitoring of the particle
concentration indicates an
alarm.
P-0-1427 > P-0-1389[68]
The monitoring of the filter
contamination indicates an
alarm.
(P-0-1273 – S-0-0813)
> P-0-1389[31]
The monitoring of the oil
temperature indicates an alarm.
P-0-1280 > P-0-1389[28]
The monitoring of the oil
temperature indicates an alarm.
P-0-1280 < P-0-1389[27]
The monitoring of the air
inclusion indicates an alarm.
P-0-1270 > P-0-1389[8]
The monitoring of the relative
humidity indicates an alarm.
P-0-1272 > P-0-1389[14]
The monitoring of the leakage
flow indicates an alarm.
P-0-1293 > P-0-1389[40]
Remedy
▶
Check/reduce the oil volume in the tank.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check/increase the oil volume in the tank.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Change the oil.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Change the oil.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Change the oil.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Change the oil.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Replace the filter element of the pressure filter.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Reduce the load.
▶
Check the oil cooling pump.
▶
Check the water cooling unit.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Heat the oil.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check the degassing function.
▶
Reduce the required flow.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check the drainage function.
▶
Reduce the required flow.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check the pump and replace it, if necessary.