8-44
Warning Diagnostic Messages (Exxxx)
E2818 Phase failure
Cause
Mains circuit breaker defective
Incorrect wiring
E2819 Mains failure
Cause
Mains circuit breaker defective
Incorrect wiring
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Supply Unit:
A single-phase mains failure was detected. Power is not switched off
unless undervoltage occurs in the DC bus (F2026).
Remedy
Replace mains circuit breaker
Check and correct wiring
E2818 - Attributes
Display:
E2818
Mess. no.:
E2818 (hex)
Supported by Firmware Variant:
Supported by Supply Unit:
A two-phase or three-phase mains failure was detected. Power is not
switched off unless undervoltage occurs in the DC bus (F2026).
Remedy
Replace mains circuit breaker
Check and correct wiring
E2819 - Attributes
Display:
E2819
Mess. no.:
E2819 (hex)
Rexroth IndraDrive
HMV01
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
DOK-INDRV*-GEN-**VRS**-WA01-EN-P