7-126
Error Messages
F2834 Contactor control error
Cause
Mains contactor could not be switched
Contactor monitor has detected an error
F2836 Error balancing monitor/ground fault
Cause
F2836 is signaled during loading of DC bus ("soft
start")
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Supply Unit:
The mains contactor could not be switched on or dropped out during
operation.
Remedy
Replace device
Replace device
F2834 - Attributes
Display:
F2834
Mess. no.:
F2834 (hex)
Supported by Firmware Variant:
Supported by Supply Unit:
Unbalance was detected for supply unit HMV01.1 / converter HCS03
during the loading of the DC bus capacitances.
Remedy
Replace device
F2836 - Attributes
Display:
F2836
Mess. no.:
F2836 (hex)
Rexroth IndraDrive
HMV01
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
DOK-INDRV*-GEN-**VRS**-WA01-EN-P