GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual page 259

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

8 COMMUNICATIONS
Table 8–6: 745 MEMORY MAP (Sheet 33 of 57)
GROUP
ADDR
DESCRIPTION
(HEX)
1E1F
Reserved
SIMULATION
1E20
Simulation Function
SETUP
1E21
Block Operation of Outputs
1E22
Start Fault Mode Signal
1E23
Start Playback Mode Signal
1E24
Reserved
1E27
Reserved
SIMULATION
1E28
Prefault Wdg 1 Phase ABC Current Magnitudes
PREFAULT
1E29
Prefault Wdg 2 Phase ABC Current Magnitudes
VALUES
1E2A
Prefault Wdg 3 Phase ABC Current Magnitudes
1E2B
Prefault Voltage Input Magnitude
1E2C
Reserved
1E2F
Reserved
SIMULATION
1E30
Fault Winding 1 Phase A Current Magnitude
FAULT VALUES
1E31
Fault Winding 1 Phase A Current Angle
1E32
Fault Winding 1 Phase B Current Magnitude
1E33
Fault Winding 1 Phase B Current Angle
1E34
Fault Winding 1 Phase C Current Magnitude
1E35
Fault Winding 1 Phase C Current Angle
1E36
Fault Winding 1 Ground Current Magnitude
1E37
Fault Winding 1 Ground Current Angle
1E38
Fault Winding 2 Phase A Current Magnitude
1E39
Fault Winding 2 Phase A Current Angle
1E3A
Fault Winding 2 Phase B Current Magnitude
1E3B
Fault Winding 2 Phase B Current Angle
1E3C
Fault Winding 2 Phase C Current Magnitude
1E3D
Fault Winding 2 Phase C Current Angle
1E3E
Fault Winding 2 Ground Current Magnitude
1E3F
Fault Winding 2 Ground Current Angle
1E40
Fault Winding 3 Phase A Current Magnitude
1E41
Fault Winding 3 Phase A Current Angle
1E42
Fault Winding 3 Phase B Current Magnitude
1E43
Fault Winding 3 Phase B Current Angle
1E44
Fault Winding 3 Phase C Current Magnitude
1E45
Fault Winding 3 Phase C Current Angle
1E46
Fault Winding 3 Ground Current Magnitude
GE Power Management
RANGE
0.0 to 40.0
0.0 to 40.0
0.0 to 40.0
0.0 to 2.0
0.0 to 40.0
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
0 to 359
0.0 to 40.0
745 Transformer Management Relay
8.3 MODBUS MEMORY MAP
STEP
UNITS
FORMAT
VALUE
---
---
---
---
---
---
---
---
---
---
---
---
× CT
0.1
× CT
0.1
× CT
0.1
× VT
0.1
× CT
0.1
---
---
°
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
1
° Lag
× CT
0.1
FACTORY
CODE
DEFAULT
F48
0 = Disabled
F67
255 = 12345678
F88
0 = Disabled
F88
0 = Disabled
10 = 1.0 × CT
F2
10 = 1.0 × CT
F2
10 = 1.0 × CT
F2
10 = 1.0 × VT
F2
10 = 1.0 × CT
F2
F1
10 = 1.0 × CT
F2
F1
120° Lag
10 = 1.0 × CT
F2
F1
240° Lag
F2
0.0 x CT
F1
0° Lag
10 = 1.0 × CT
F2
F1
0° Lag
10 = 1.0 × CT
F2
F1
120° Lag
10 = 1.0 × CT
F2
8
F1
240° Lag
0.0 × CT
F2
F1
0° Lag
10 = 1.0 × CT
F2
F1
330° Lag
10 = 1.0 × CT
F2
F1
90° Lag
10 = 1.0 × CT
F2
F1
210° Lag
0.0 × CT
F2
8-49