GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual page 131

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

5 SETPOINTS
As mentioned above, the parameters of an equation can contain either INPUTS or GATES.
Table 5–6: FLEXLOGIC™ INPUT TYPES
INPUTS
INPUT IS "1" (= ON) IF...
element* pickup
the pickup setting of the element is exceeded
element* operate
the pickup setting of the element is exceeded for the programmed time delay
logic inputs 1 to 16
the logic input contact is asserted
virtual inputs 1 to 16
the virtual input is asserted
output relays 1 to 8
the output relay operates
(i.e. evaluation of the FlexLogic™ equation results in a '1')
virtual outputs 1 to 5
the virtual output operates
(i.e. evaluation of the FlexLogic™ equation results in a '1')
timers 1 to 10
the timer runs to completion
(i.e. the 'start' condition is met for the programmed time delay)
* element refers to any protection or monitoring element programmed under page S4 ELEMENTS
Table 5–7: FLEXLOGIC™ GATES
GATES
NUMBER OF INPUTS
NOT
1
OR
2 to 19 (for 20 parameter equations)
2 to 9 (for 10 parameter equations)
AND
2 to 19 (for 20 parameter equations)
2 to 9 (for 10 parameter equations)
NOR
2 to 19 (for 20 parameter equations)
2 to 9 (for 10 parameter equations)
NAND
2 to 19 (for 20 parameter equations)
2 to 9 (for 10 parameter equations)
XOR
2 to 19 (for 20 parameter equations)
2 to 9 (for 10 parameter equations)
Inputs and gates are combined into a FlexLogic™ equation. The sequence of entries in the linear array of
parameters follows the general rules listed in the following section.
GE Power Management
OUPUT IS "1" (= ON) IF...
input is '0'
any input is '1'
all inputs are '1'
all inputs are '0'
any input is '0'
odd number of inputs are '1'
745 Transformer Management Relay
5.7 S5 OUTPUTS