Panasonic EBL128 Operating Instructions Manual page 19

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
Push buttons on the Fire Brigade Panel (FBP)
Push button
P1
Alarms queued (black)
P2
Silence buzzer
(yellow)
P3
Silence Alarm devices
5
(red)
P4
Reset (green)
P5
Evacuate (green)
Alert Annunciation
Acknowledge (green)
Disable (yellow)
Operation/function
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
Used to silence the buzzer in EBL128
Used to silence the sounders (i.e. to "reset" outputs for alarm
6
devices).
Used to reset the fire alarm(s).
sec.
8
Used to activate all the sounders (i.e. the outputs for alarm
devices).
Used to acknowledge an Alert Annunciation alarm.
9
10
Used to disables all zones in alarm state.
5
In the New Zealand convention = The "inside switch".
6
Via EBLWin can be set if the alarm devices shall be continuous off /
disabled or re-sound for a new alarm.
7
Single reset: The fire alarm displayed in the LCD (first row to the left)
will be reset. When more than one fire alarm is activated (LEDs "Alarms
queued" are lit) each fire alarm has to be individually reset.
Multiple reset (Default): All fire alarms will be reset simultaneously.
Single encapsulated reset: Like Single reset but with the Encapsulation
function, which is described in chapter "Single with automatic disablement",
page 55.
NOTE (1)! When "Multiple reset" is used, encapsulated reset can be done
by pressing "Reset" (P4) and 0.1 sec. later also press "Alarms queued" (P1)
and hold them pressed for > 0.5 sec. The fire alarm displayed in the LCD
(first row to the left) will be encapsulated or the points in alarm status within
one zone will be encapsulated or the whole zone (conventional) will be
encapsulated.
NOTE (2)! When "Single encapsulated reset" is used, you can make a
"Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also press "A" (in
the keypad) and hold them pressed for > 0.5 sec.
8
"Evacuate" is only valid in the "Belgian", Brittish Standard, Hungarian,
Spanish and "Ukrainian" conventions.
9
"Alert Annunciation Acknowledge" is only valid in the "Czech", Bulgarian
and "Polish" conventions.
10
"Disable" is only valid in the "Australian" and New Zealand conventions.
17
EBL128 Operating Instructions V2.0.x
7
Has to be pressed for > 0.5