Disable Interlocking Output (H9/C4) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
32.4
Action
"Access"
Scroll to menu H9.
"A"
Scroll to menu C4.
"A"
E.g. "01", "01"
"A"
"A"
"A"
"Return"
Rev: -

Disable interlocking output (H9/C4)

Up to 100 Interlocking outputs (Type = Interlocking) can be
individually disabled via this menu but not via menu H2.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output.
disabled via menu H2/B4.
Disabled interlocking outputs are listed in menu H4/U1.
The LED "Disablements" (L8) is also indicating one or more disabled
interlocking outputs.
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Disable interlocking output
Disable interlocking output
area 00 point 00
Disable interlocking output
area 01 point 01
Interlocking output 01-01 disabled
Disable interlocking output
Interlocking outputs and inputs
EBL128 Operating Instructions V2.0.x
All interlocking outputs can be collectively
ACCEPT? H9
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? H9
141
Comments
According to chapter
"Access", see page 81.
C1
C4
Press "A" to accept and/or
"Return" to menu C4.
Scroll or press "Return" to
C4
menu H9.
Scroll or press "Return".