Restore Weekly Average To Default (H8/S5) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
31.5
Action
"Access"
Scroll to menu H8.
"A"
Scroll to menu S5.
"A"
E.g. "01-01"
"A"
"A"
"Return"
"Return"
Rev: -

Restore weekly average to default (H8/S5)

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
restored and set to a default value. If not, the new / clean sensor will
inherit the old sensor's value. The week average sensor value has to
be restored for each replaced sensor individually. First replace the
sensor then restore the week average sensor value as soon as
possible.
The very first week average sensor value after restoring will be
calculated within one hour. Thereafter a new average sensor value
will be calculated each week.
NOTE!
Authorised service personnel only, must use this menu.
Used incorrectly it can cause nuisance fire alarms from a sensor or no
fire alarm at all.
Text in display
Maintenance
Disconnect / Re-connect COM loop
Restore weekly average to default
Enter zone-address to restore: 00-00
Sensor 01-01 (tech addr 001) is restored
to default average
Enter zone-address to restore: 00-00
Restore weekly average to default
Maintenance
EBL128 Operating Instructions V2.0.x
ACCEPT? H8
ACCEPT? S1
ACCEPT? S5
ACCEPT?
ACCEPT?
ACCEPT? S5
ACCEPT? H8
130
Comments
According to chapter
"Access", see page 81.
Write the zone-address and
press "A" to accept.
If more sensors shall be
restored, continue like
above. If not, press
"Return" to menu S5.
Scroll or press "Return" to
menu H8.
Scroll or press "Return".

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents