GE 339 Instruction Manual page 76

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

FRONT CONTROL PANEL INTERFACE
3–10
Table 3-1: Minor Self-test Errors
Self-test Error
Latched
Message
Target
Message?
MAINTENANCE
No
ALERT: IRIG-B
Failure
MAINTENANCE
No
ALERT: Clock
Not Set
MAINTENANCE
No
ALERT: Comm
Alert 1, 2, or 3
MAINTENANCE
No
ALERT :
Ethernet Link
Fail
MAINTENANCE
No
ALERT: High
Ethernet
Traffic
MAINTENANCE
No
ALERT: High
Ambient
Temperature
MAINTENANCE
No
ALERT:
Daughter Error
MAINTENANCE
No
ALERT: Comms
Serial Invalid
MAINTENANCE
No
ALERT: RMIO
Mismatch
* Failure is logged after the detection of 5 consecutive failures - that is after 25 seconds
Description of
How Often the Test
Problem
is Performed
A bad IRIG-B input
Every 5 seconds*
signal has been
detected.
Clock time is the
Every 5 seconds*
same as the default
time.
Communication
Every 5 seconds*
error between CPU
and Comms board.
Communication
Detected
error between
Instantaneously
339 and Network.
Every 5 seconds*
The ambient
Every 1 hour
temperature is
o
above 80
C.
The rear
Every 5 seconds*
Communications
daughter board type
does not match the
order code.
The internal
Every 5 seconds*
communications
board does not
match the order
code.
RMIO Module is not
Every 5 seconds*
validated;
communications
with the RMIO
module are lost or
interrupted.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INTERFACES
What to do
Ensure IRIG-B cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), ensure
IRIG-B receiver is
functioning, and check
input signal level (it may
be less than specification).
If none of these apply,
contact the factory.
Set the date and time in
S1 RELAY SETUP.
If alert doesn't self-reset,
then contact factory.
Otherwise monitor
recurrences as errors are
detected and self-reset.
Check Ethernet cable and
Ethernet connection.
Check health of the
network. Check status of
external routers and
switches. Check that IP
settings are not 0.0.0.0
Increase ventilation to the
surroundings.
Replace the rear
communications
daughter board with the
correct board.
Contact factory.
Validate the RMIO Module;
check CANBUS
communication.

Advertisement