S3 PROTECTION
NOTE:
NOTE
6–98
The availability of assignable Output Relay setpoints is dependent on the Order Code
options and the SWITCHING DEVICE setpoint. For more information refer to section S5
INPUTS/OUTPUTS > OUTPUT RELAYS and to
To select any assignable output relays to operate upon the RTD #1 to 12 Alarm
operation, assign the Logic Operand "RTD #1 to 12 ALARM OP" or "Any Alarm OP" to a
Logic Element.
e.g. With the following setup, output relay 5 will operate upon the operation of any RTD
or alarm.
S3 RTD #1
RTD #1 APPLICATION
Stator
RTD #1 NAME
RTD1
RTD #1 ALARM
Enabled
RTD #1 ALARM TEMP
130°C
RTD #1 ALARM PKP DELAY
2.00 s
RTD #1 ALARM DPO DELAY
2.00 s
RTD #1 TRIP
Disabled
RTD #1 TRIP TEMP
155°C
RTD #1 TRIP PKP DELAY
2.00 s
RTD #1 TRIP DPO DELAY
2.00 s
RTD #1 TRIP VOTING
Off
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
BLOCK 1 to 3
For details see
Common
Common
S4 LOGIC ELEMENT 1
LOGIC E 1 NAME
Alarm Operation
LOGIC E1 FUNCTION
Enabled
LOGIC E1 ASSERTED
On
TRIGGER SOURCE 1
Any Alarm OP
TRIGGER SOURCE 2
Off
TRIGGER SOURCE 3
Off
PICKUP TIME DELAY
0 ms
DROPOUT TIME DELAY
0 ms
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
setpoints.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
setpoints.
896802A2.cdr