CHAPTER 6: SETPOINTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Path:
S6 MONITORING > DEMAND > APPARENT PWR DEMAND
FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
For details see
Common
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Dmd
Default: Blk Interval
This setpoint sets the measurement method. Three methods can be applied.
THERMAL 90% RESPONSE TIME
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 15 min
This setpoint sets the time required for a steady state Apparent Power to indicate 90% of
the actual value and allows the user to approximately match the response of the relay
to analog instruments. The setpoint is visible only if MEASUREMENT TYPE is "Exponential".
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 20 min
This setpoint sets the time period over which the Apparent Power Demand calculation is
to be performed. The setpoint is visible only if MEASUREMENT TYPE is "Block Interval" or
"Rolling Demand".
PICKUP
Range: 0.1 to 300000.0 kVA in steps of 0.1 kVA
Default: 1000.0 kVA
This setpoint sets the Apparent Power Demand Pickup level.
BLOCK
For details see
Common
OUTPUT RELAY X
For details see
Common
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
setpoints.
setpoints.
setpoints.
S6 MONITORING
6–177