CHAPTER 6: SETPOINTS
"..operand name..Trip PKP"
"..operand name.. Trip OP"
"..operand name.. Trip DPO"
"..operand name..Alarm PKP"
"..operand name.. Alarm OP"
"..operand name.. Alarm DPO"
"..operand name.. Block"
"..operand name.. Off
"..operand name.. On
Element
Operands
Contact Inputs
Contact IN 1..10 On
Contact IN 1..10 Off
Virtual Inputs
Virtual IN 1..32 On
Virtual IN 1..32 Off
Remote Inputs
Remote IN 1..32 On
Remote IN 1..32 Off
General
Off
On
Any Trip
Any Alarm
Any Pkp OP
Any Block
Any Inhibit
Output Relay 1 On
Output Relay 2 On
Output Relay 3 On
Output Relay 4 On
Output Relay 5 On
Output Relay 6 On
Output Relay 1 Blk
Output Relay 2 Blk
BKR Connected
Open Breaker
Close Breaker
Maint. Req.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Operand types and descriptions
The following tables of Logic Operands, taken from Function Code FC134B in the 3 Series
Communications Guide, show the list of available Logic Inputs. Where specific event
descriptions are not given, a general description applies as follows:
General descriptions of operands originating from protection, control, and monitoring
elements:
The function setpoint of the element has been programmed as "Trip" and the element picked up
The function setpoint of the element has been programmed as "Trip" and the element operated
The function setpoint of the element has been programmed as "Trip" and the element operation
dropped out
The function setpoint of the element has been programmed as "Alarm" and the element picked up
The function setpoint of the element has been programmed as "Alarm" and the element operated
The function setpoint of the element has been programmed as "Alarm" and the element operation
dropped out
The operation of the element has been blocked
General descriptions of operands originating from digital elements such as contact, virtual
and Remote inputs, Output Relays, and Virtual Outputs:
"The status of the selected input or output is OFF
"The status of the selected input or output is ON
Event Description
Generated upon operation of any element with function setpoint set to "Trip"
Generated upon operation of any element with function setpoint set to "Alarm"
Generated upon detection of pickup status from any element
Generated when the operation of any element is blocked
Generated when the operation of any element is inhibited
Defines the status of the breaker in the power system. BKR Connected means breaker
racked in the system
Defines a command to open the breaker
Defines a command to close the breaker
S4 CONTROLS