Chapter 6 - Parameter Description [FU1]
FU1-30 ~ FU1-37: User V/F Frequency and
Voltage
FU1? User freq 1
30
15.00 Hz
Factory Default:
15.00 Hz
FU1? User volt 1
31
25 %
Factory Default:
25 %
FU1? User freq 4
36
60.00 Hz
Factory Default:
60.00 Hz
FU1? User volt 4
37
100 %
Factory Default:
100 %
These functions are available only when ' User V/F' is
selected in FU1-29 [V/F pattern]. Users can make the
custom V/F pattern by setting four points between FU1-
22 [Starting Frequency] and FU1-21 [Base Frequency].
Output Voltage
100%
FU1-37
FU1-35
FU1-33
FU1-31
FU1-30
FU1-32
[User V/F]
Note: When the ' User V/F' is selected, the torque boost
of FU1-26 through FU1-28 is ignored.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
30
15.00
15.00
31
25
25
36
60.00
60.00
37
100
100
Output
Frequency
FU1-36
FU1-34
Freq. Base
Related Functions:
FU1-21 [Base Frequency]
FU1-22 [Starting Frequency]
FU1-29 [Volts/Hz Pattern]

FU1-38: Output Voltage Adjustment

FU1?Volt control
38
100.0 %
Factory Default:
100.0 %
This function is used to adjust the output voltage of the
inverter. This is useful when using a motor with a lower
rated voltage than the main input voltage. When this is
set at 100%, inverter outputs its rated voltage.
Output Voltage
100%
50%
Note: The inverter output voltage does not
exceed the main input voltage, even though
FU1-38 is set at 110%.

FU1-39: Energy Save Level

FU1? Energy save
39
0 %
Factory Default:
0 %
This function is used to reduce the output voltage in
applications that do not require high torque and current
at its steady speed. The inverter reduces its output
voltage after accelerating to the reference frequency
(steady speed) if the energy save level is set at 20%.
This function may cause over-current trip due to the lack
of output torque in a fluctuating load.
This function does not work with 0% set point value.
94
38
100
100
When set at 50%
Output
Frequency
FU1-21 [Base Freq]
39
0
0