Chapter 6 - Parameter Description [APP]
♦ Abnormal motor can be skipped from running by
using the multi-function input terminals (P1, P2, P3, and
P4). If a multi-function terminal is opened, the inverter
stops all running motors and restarts operation with only
normal motors except the abnormal motor. (Refer to
APP-29)
♦ Sleep function is initiated when flow demand is low.
Inverter stops motor when the motor runs below Sleep
Frequency (APP-24) during Sleep Delay Time (APP-23).
While in the sleep state, inverter keeps monitoring and
initiates Wake-Up function when the real value of the
controlling amount has decreased below the Wake-Up
level (APP-25).
Note: Only one auxiliary motor can be connected with
AUX terminal on control t e rminal strip without using MMC
Option Board.
Related Functions:
APP-08 to APP-31 [MMC Parameters]
DRV-04 [Frequency Mode]
FU2-47 [PID Operation Selection]
I/O-01 to I/O-10 [Analog Signal Input]
EXT 15 to EXT21 [Pulse Input Signal]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-30 to EXT-32 [Multi-Function Output]
Input
MMC Board
Power
iS5
RLY1
RLY2
RLY3
V1
V2
I
AUX
M
[MMC Diagram]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Aux. Motor 1
M1
Aux. Motor 2
M2
Aux. Motor 3
M3
Aux. Motor 4
M4
Main Motor
[Draw]: This is a kind of Open-Loop Tension Control.
This is used to maintain constant tension of material with
the speed difference between main motor and
subordinate motor.
Related Functions:
APP-32 to APP-33 [Draw Parameters]
DRV-04 [Frequency Mode]
I/O-01 to I/O-10 [Analog Signal Input]
EXT 06 to EXT-10 [Analog Input Setting]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-02 to EXT-04 [Multi-Function Input]

APP-02: Traverse Amplitude

APP?Trv. Amp[%]
02
0.0%
Factory Default:
0.0%
This code sets the frequency amplitude of traverse
operation. The value is the percentage of reference
frequency. The output value is determined by,
Trv. Amp Frequency = (Reference Freq. * Trv. Amp)/100

APP-03: Traverse Scramble Amplitude

APP?Trv. Scr[%]
03
0.0%
Factory Default:
0.0%
This code sets the frequency amplitude of scramble
operation. The output value is determined by,
Trv. Scr Frequency = (Trv. Amp Frequency * (100 - Trv.
Scr))/100

APP-04: Traverse Accel Time

APP-05: Traverse Decel Time

APP?Trv Acc Time
04
2.0 sec
Factory Default:
2.0 sec
APP?Trv Dec Time
05
3.0 sec
Factory Default:
3.0 sec
Sets the acceleration and deceleration time for traverse
operation.
146
02
0.0
0.0
03
0.0
0.0
04
2.0
2.0
05
3.0
3.0