Sign In
Upload
Manuals
Brands
Schweitzer Engineering Manuals
Controller
SEL-351P
Schweitzer Engineering SEL-351P Manuals
Manuals and User Guides for Schweitzer Engineering SEL-351P. We have
1
Schweitzer Engineering SEL-351P manual available for free PDF download: Quick Start Manual
Schweitzer Engineering SEL-351P Quick Start Manual (674 pages)
Brand:
Schweitzer Engineering
| Category:
Controller
| Size: 6 MB
Table of Contents
Table of Contents
3
Introduction
7
About this Quick-Start Installation and User's Guide
7
Safety Information
7
Installation
9
Figure 1: SEL-351P Recloser Control Dimensions and Panel Cutout
9
Figure 2: SEL-351P Recloser Control Side Panel
10
Figure 3: SEL-351P Relay Inputs, Outputs, and Communications Ports
11
Figure 4: Trip and Close Circuit, Breaker Status, and SF6 Pressure Connections
12
Extra I/O
13
Mounting
13
Mounting Holes
13
Panel Cutout
13
Side Panel Connections
13
Wire Harness Mounting
13
Current Inputs
14
User-Supplied Connectors
14
Voltage Inputs
14
12 VDC Power Output
15
120 Vac Power Input
15
24 VDC Battery
15
24 VDC Whetting Voltage
16
Capacitor Charger Power
16
Capacitor Voltage Monitor and Charger Control
16
CONTROL Connector J5 Details
16
Trip and Close Output Contacts
16
Checks before the SEL-351P Is Put in Service
17
SF6 Pressure Sensor
17
Communications
18
Getting Started with Communications
18
Communications Connections Example
19
Figure 5: SEL-351P Recloser Control Communications Connections Example
19
Serial Ports
20
Serial Port Default Settings
20
EIA-232 Pinout Functions for Ports 2, 3, and F
20
Pinout Functions for Port 1
21
Serial Communications Port Pin Function Definitions
21
Communications Cables
21
Table 1: SEL EIA-232 Serial Communications Cable Guide
21
Cable Diagrams
22
Commands
22
Table 2: SEL-351P Recloser Control Command Summary
23
Event Reports
26
Access Levels and Password Protection
27
Table 3: Event Report Parameters
27
View or Change Passwords
28
Disable Passwords
28
Table 4: Access Level, Summary Information
28
Password Jumper
29
Figure 6: Jumper, Connector, and Major Component Locations on the SEL-351P Recloser Control Main Board
30
Front-Panel Interface
31
Figure 7: SEL-351P Recloser Control Front-Panel Interface
31
Figure 8: Status and Trip Target Leds
32
Figure 9: Primary and Secondary Functions of Front-Panel Pushbuttons
32
Pushbuttons
32
Status and Trip Target Leds
32
Table 5: Front-Panel Pushbutton Secondary Functions
33
Pushbutton Primary Functions
34
Operator Controls
37
Settings
40
Curve Information
40
Table 6: Recloser Curve Designations
41
Table 7: US, IEC, and User-Programmable Curve Designations
41
Factory EZ Settings
42
Table 8: EZ Settings Quick Reference
43
Settings Descriptions
45
Settings Groups 1 (Main) and 2 (Alternate) EZ Settings
45
Table 9: Seconds-To-Cycles Conversion (60 Hz)
52
Global EZ Settings
66
Table 10: Recloser Interrupt Data
66
Testing
73
Testing the SEL-351P Recloser Control Without Regularly Installed Apparatus
73
Front Panel Status Leds
73
Logic Settings Changes
73
Figure 10: Recloser Simulator Connections to SEL-351P (Only a 52A Available)
74
Output Contacts
74
Recloser Simulator
74
Overcurrent Element Timing Test Setup
75
Battery
76
Battery Operation Overview
76
Battery-Related Settings
76
Battery Status
76
Battery Status Via Front Panel
76
Battery Status Via Serial Port
77
Automatic Battery Load Test
77
Battery Load Test Via Front Panel
78
Battery Load Test Via Serial Port
78
Specifications
80
Relay Element Pickup Ranges and Accuracies
82
Instantaneous/Definite-Time Overcurrent Elements
82
Time-Overcurrent Elements
82
Synchronism-Check Elements
83
Timers
83
Under- and Overfrequency Elements
83
Under- and Overvoltage Elements
83
Metering Accuracy
84
Factory Assistance
84
Standard Product Warranty
85
Definition of Terms
85
New Product Warranty
85
Product Upgrade Policy
85
Equipment Repair and Warranty
85
Limitations
86
Section 1: Factory-Set Logic
93
Introduction
97
Factory Default Settings
97
Installation Variations and Logic Changes
97
EZ Settings Vs. "Regular" Settings
97
Overcurrent Element Functions Overview
101
Residual Ground Vs. Neutral Ground
102
Section 1: Factory-Set Logic
97
Cold Load Pickup Scheme
103
Enable Cold Load Pickup Scheme
103
Start Loss of Load Diversity Timer
104
Actively Engage Cold Load Pickup Scheme (Phase Elements Example)
105
Use Overcurrent Element Torque Control Logic to Enable/Disable or Desensitize Elements (Phase Elements Example)
107
Desensitize Delay Curve - Maintain Coordination (Phase Elements Example)
107
Disengage Cold Load Pickup Scheme (Phase Elements Example)
108
Other Cold Load Pickup Scheme Details Involving Ground and SEF Elements
108
Fast Curve Operation Logic
109
Fast Curve Operation When Reclosing Is Defeated
110
Logic
113
High Current Trip Operation When Reclosing Is Defeated
113
Trip Logic
124
Close Logic
125
Close Conditions - Other than Auto-Reclosing
125
Unlatch Close Conditions
126
Recloser Status
127
Operations to Lockout
128
High-Current Lockout
129
Other Drive-To-Lockout Conditions
130
Block Reset Timing
132
Sequence Coordination
133
Reclose Supervision Logic
136
Trip and Close Capacitors Charged
137
Healthy Battery
137
Operator Control Logic
137
Detailed Operator Control Pushbutton Output
139
TERRA HABILITADO Operator Control Pushbutton Output
139
BLOQUEIO Operator Control Pushbutton Output
140
Other Operator Control Pushbutton Outputs Operate Similarly to TERRA HABILITADO
140
ABRIR and FECHAR Operator Control Pushbutton Outputs
141
Corresponding Operator Control Leds and Logic Applications
143
TERRA HABILITADO Operator Control
144
Section 2: Additional Installation Details
155
Extra Alarm" Output Contact Control Jumper
157
Introduction
157
Output Contact Jumpers
157
Section 2: Additional Installation Details
157
Password and Breaker Jumpers
159
Clock Battery
160
Voltage Connections
160
Installation with Only 120 Vac Power (Traditional Installation)
163
Front-Panel AC SUPPLY LED
163
Installation with Separate 120 Vac Power and Three-Phase Voltage
163
Undervoltage Block for Frequency Elements
164
Installation with Separate 120 Vac Power, Three-Phase, and Synchronism Check Voltage
164
Front-Panel AC SUPPLY LED
164
Installation with Only Three-Phase Voltage (120 Vac Power Provided by Three-Phase Voltage)
164
Voltage
164
Section 3: Overcurrent, Voltage, Synchronism Check, and Frequency Elements/Section 3: Overcurrent, Voltage, Synchronism Check, and Frequency Elements
165
Voltage)
166
Instantaneous/Definite-Time Overcurrent Elements
169
Phase Instantaneous/Definite-Time Overcurrent Elements
169
Accuracy
169
Settings Ranges
169
Pickup Operation
171
Directional Control Option
173
Torque Control
173
Combined Single-Phase Instantaneous Overcurrent Elements
174
Pickup and Reset Time Curves
174
Phase-To-Phase Instantaneous Overcurrent Elements
175
Accuracy
176
Pickup and Reset Time Curves
176
Pickup Operation
176
Setting Range
176
Neutral Ground Instantaneous/Definite-Time Overcurrent Elements
176
Accuracy
179
Pickup and Reset Time Curves
179
Settings Ranges
179
Residual Ground Instantaneous/Definite-Time Overcurrent Elements
180
Accuracy
181
Pickup and Reset Time Curves
181
Settings Ranges
181
Negative-Sequence Instantaneous/Definite-Time Overcurrent Elements
182
Accuracy
182
Pickup and Reset Time Curves
182
Settings Ranges
182
Section 3: Overcurrent, Voltage, Synchronism Check, and Frequency Elements
169
Time-Overcurrent Elements
184
Phase Time-Overcurrent Elements
184
Settings Ranges
184
Accuracy
187
Logic Outputs (51P1T Element Example)
187
Torque Control Switch Closed
187
Torque Control Switch Operation (51P1T Element Example)
187
Control of Logic Point TCP1
188
Directional Control Option
188
Torque Control Switch Open
188
Torque Control
189
Reset Timing Details (51P1T Element Example)
190
Setting 51P1RS = N
190
Setting 51P1RS = y
190
Neutral Ground Time-Overcurrent Elements
190
Accuracy
192
Settings Ranges
192
Residual Ground Time-Overcurrent Elements
192
Accuracy
194
Negative-Sequence Time-Overcurrent Element
195
Accuracy
196
Settings Ranges
196
Voltage Elements
197
Voltage Element Settings
197
Accuracy
202
Voltage Element Operation
202
Undervoltage Element Operation Example
202
Overvoltage Element Operation Example
203
Voltage Elements Used in POTT Logic
203
Synchronism Check Elements
203
Synchronism Check Elements Settings
204
Accuracy
204
Synchronism Check Elements Voltage Inputs
206
Synchronism Check Elements Operation
206
And V
207
Other Uses for Voltage Window Elements
207
System Frequencies Determined from Voltages V
207
Voltage Window
207
Block Synchronism Check Conditions
208
Angle Difference Calculator
209
Are "Slipping
209
P and V S Are "Static
209
Voltages V
209
Are "Slipping")
211
P and
211
Synchronism Check Element Outputs
212
Synchronism Check Applications for Automatic Reclosing and Manual Closing
213
Frequency Elements
214
Frequency Element Settings
214
Accuracy
216
Create Over- and Underfrequency Elements
216
Overfrequency Element
217
Underfrequency Element
217
Frequency Element Operation
217
Overfrequency Element Operation
217
Frequency Element Voltage Control
218
Other Uses for Undervoltage Element 27B81
218
Underfrequency Element Operation
218
Frequency Element Uses
218
Section 4: Loss-Of-Potential, Load Encroachment, and Directional Element Logic/Section 4: Loss-Of-Potential, Load Encroachment, and Directional Element Logic
219
Loss-Of-Potential Logic
223
Setting ELOP = y or Y1
224
Setting ELOP = y
224
Setting ELOP = N
224
Section 4: Loss-Of-Potential, Load Encroachment, and Directional Element Logic
223
Load-Encroachment Logic
225
Settings Ranges
226
Load-Encroachment Setting Example
226
Convert Maximum Loads to Equivalent Secondary Impedances
226
Convert Power Factors to Equivalent Load Angles
227
Apply Load-Encroachment Logic to a Phase Time-Overcurrent
227
Use SEL-321 Relay Application Guide for the SEL-351P Recloser Control
229
Internal Enables
230
Best Choice Ground Directional™ Logic
231
Directional Elements
231
Directional Element Routing
231
Loss-Of-Potential
232
Direction Forward/Reverse Logic
232
Internal Enables
242
Directional Elements
243
Directional Element Routing
243
Loss-Of-Potential
243
Direction Forward/Reverse Logic
244
Directional Control Settings
249
Settings Made Automatically
249
Settings
250
DIR1 - Level 1 Overcurrent Element Direction Setting
250
DIR2 - Level 2 Overcurrent Element Direction Setting
250
DIR3 - Level 3 Overcurrent Element Direction Setting
250
DIR4 - Level 4 Overcurrent Element Direction Setting
250
ORDER - Ground Directional Element Priority Setting
251
50P32P - Phase Directional Element Three-Phase Current Pickup
252
Z2F - Forward Directional Z2 Threshold
252
Z2F and Z2R Set Automatically
252
Z2R - Reverse Directional Z2 Threshold
252
50QFP - Forward Directional Negative-Sequence Current Pickup
253
50QFP and 50QRP Set Automatically
253
50QRP - Reverse Directional Negative-Sequence Current Pickup
253
A2 - Positive-Sequence Current Restraint Factor, I
253
A2 Set Automatically
253
K2 - Zero-Sequence Current Restraint Factor, I
254
K2 Set Automatically
254
50GFP - Forward Directional Residual Ground Current Pickup
255
50GFP and 50GRP Set Automatically
255
50GRP - Reverse Directional Residual Ground Current Pickup
255
A0 - Positive-Sequence Current Restraint Factor, I
255
A0 Set Automatically
255
Z0F - Forward Directional Z0 Threshold
256
Z0F and Z0R Set Automatically
256
Z0R - Reverse Directional Z0 Threshold
256
E32Iv - Sel Ogic
256
Directional Control Provided by Torque Control Settings
257
Section 5: Trip and Target Logic
259
Section 5: Trip and Target Logic
263
Set Trip
265
Unlatch Trip
266
Other Applications for the Target Reset Function
266
Factory Settings Example (Using Setting TR)
266
Program an Output for Tripping
267
Switch-Onto-Fault (SOTF) Trip Logic
267
Three-Pole Open Logic
268
Determining Three-Pole Open Condition Without Circuit Breaker Auxiliary Contact
269
Circuit Breaker Operated Switch-Onto-Fault Logic
269
Close Bus Operated Switch-Onto-Fault Logic
269
Switch-Onto-Fault Logic Output (SOTFE)
270
Switch-Onto-Fault Trip Logic Trip Setting (TRSOTF)
270
Enable Setting ECOMM
271
Trip Setting TRCOMM
272
Trip Settings TRSOTF and TR
273
Trip Setting DTT
273
Use Existing SEL-321 Relay Application Guides for the SEL-351P Recloser Control
273
Optoisolated Input Settings Differences between the SEL-321 and SEL-351P Recloser Control
274
Trip Settings Differences between the SEL-321 and SEL-351P Recloser Control
274
Permissive Overreaching Transfer Trip (POTT) Logic
274
Use Existing SEL-321 Relay POTT Application Guide for the SEL-351P Recloser Control
275
External Inputs
275
PT1 - Received Permissive Trip Signal(S)
275
Timer Settings
276
EBLKD - Echo Block Delay
276
EDURD - Echo Duration
276
ETDPU - Echo Time Delay Pickup
276
Z3RBD - Zone (Level) 3 Reverse Block Delay
276
Logic Outputs
276
ECTT - Echo Conversion to Trip
276
KEY - Key Permissive Trip
276
Z3RB - Zone (Level) 3 Reverse Block
276
EKEY - Echo Key Permissive Trip
277
Variations for Permissive Underreaching Transfer Trip (PUTT) Scheme
279
Installation Variations
279
Directional Comparison Unblocking (DCUB) Logic
280
Use Existing SEL-321 Relay DCUB Application Guide for the SEL-351P Recloser Control
281
External Inputs
281
LOG1, LOG2 - Loss-Of-Guard Signal(S)
281
PT1, PT2 - Received Permissive Trip Signal(S)
281
Timer Settings
282
GARD1D - Guard-Present Delay
282
UBDURD - DCUB Disable Delay
282
UBEND - DCUB Duration Delay
282
Logic Outputs
282
UBB1, UBB2 - Unblocking Block Output(S)
282
PTRX1, PTRX2 - Permissive Trip Receive Outputs
285
Installation Variations
285
Use Existing SEL-321 Relay DCB Application Guide for the SEL-351P Recloser Control
286
External Inputs
287
BT - Received Block Trip Signal(S)
287
Timer Settings
287
67P2SD, 67N2SD, 67G2SD, 67Q2SD - Level 2 Short Delay
287
BTXD - Block Trip Receive Extension
287
Z3XD - Zone (Level) 3 Reverse Dropout Extension
287
Z3XPU - Zone (Level) 3 Reverse Pickup Time Delay
287
Logic Outputs
288
DSTRT - Directional Carrier Start
288
NSTRT - Nondirectional Carrier Start
288
STOP - Stop Carrier
288
BTX - Block Trip Extension
289
Installation Variations
289
Additional Front-Panel Status and Target LED Information
291
A, B, and C Target Leds
291
Target Reset/Lamp Test Front-Panel Pushbutton
291
Other Applications for the Target Reset Function
291
Section 6: Close and Reclose Logic
293
Close Logic
295
Set Close
296
Unlatch Close
297
Factory Settings Example
297
Defeat the Close Logic
297
Circuit Breaker Status
297
Settings and General Operation
301
Reclose Supervision Limit Time = 0 (Top of Figure 6.2)
301
Reclose Supervision Limit Time > 0 (Bottom of Figure 6.2 and Figure 6.3)
301
Set Reclose Supervision Logic (Bottom of Figure 6.2)
302
Unlatch Reclose Supervision Logic (Bottom of Figure 6.2)
302
Settings Example 1
303
SEL-351P(1) Recloser Control
303
SEL-351P(2) Recloser Control
303
Other Setting Considerations for SEL-351P(1) and SEL-351P(2) Recloser Controls
304
Settings Example 2
304
Section 6: Close and Reclose Logic
295
Reclosing Relay
305
Reclosing Relay States and General Operation
306
Lockout State
307
Reclosing Relay States and Settings/Setting Group Changes
307
Defeat the Reclosing Relay
308
Close Logic Can Still Operate When the Reclosing Relay Is Defeated
308
Reclosing Relay Timer Settings
309
Open Interval Timers
309
Determination of Number of Reclosures (Last Shot)
310
Observe Shot Counter Operation
310
Monitoring Open Interval and Reset Timing
311
Reset Timer
311
Reclosing Relay Shot Counter
312
Ogic
312
Reclose Initiate and Reclose Initiate Supervision Settings (79RI and 79RIS, Respectively)
313
Factory Settings Example
313
Additional Settings Example
314
Other Settings Considerations
314
Drive-To-Lockout and Drive-To-Last Shot Settings (79DTL and 79DLS, Respectively)
315
Factory Settings Example
315
Other Settings Considerations
316
Skip Shot and Stall Open Interval Timing Settings (79SKP and 79STL, Respectively)
316
Additional Settings Example 1
317
Additional Settings Example 2
317
Factory Settings Example
317
Additional Settings Example 3
318
Other Settings Considerations
318
Block Reset Timing Setting (79BRS)
318
Sequence Coordination Setting (79SEQ)
319
Reclose Supervision Setting (79CLS)
320
Section 7: Inputs, Outputs, Timers, and Other/Control Logic
321
Section 7: Inputs, Outputs, Timers, and Other
325
Control Logic
325
Optoisolated Inputs
325
Input Debounce Timers
326
Input Functions
327
Input IN101
327
Settings Examples
327
Local Control Switch Types
330
OFF/MOMENTARY Switch
330
ON/OFF Switch
330
ON/OFF/MOMENTARY Switch
331
Settings Examples
332
Additional Local Control Switch Application Ideas
333
Local Control Switch States Retained
333
Power Loss
333
Settings Change or Active Setting Group Change
334
Remote Control Switches
334
Changed
335
Remote Bit Application Ideas
335
Remote Bit States Not Retained When Power Is Lost
335
Latch Control Switches
335
Latch Control Switch Application Ideas
336
Reclosing Relay Enable/Disable Setting Example
337
Feedback Control
338
Rising Edge Operators
338
Use a Remote Bit Instead to Enable/Disable the Reclosing Relay
339
Latch Control Switch States Retained
340
Power Loss
340
Reset Latch Bits for Active Setting Group Change
340
Settings Change or Active Setting Group Change
340
Note: Make Latch Control Switch Settings with Care
341
Multiple Setting Groups
343
Active Setting Group Indication
343
Selecting the Active Setting Group
343
Operation of Serial Port GROUP Command and Front-Panel GROUP Pushbutton
344
Active Setting Group Switching Example 1
345
SEL-351P Disabled Momentarily During Active Setting Group Change
345
Start out in Setting Group 1
347
Switch Back to Setting Group 1
347
Switch to Setting Group 4
347
Selector Switch Now Rests on Position REMOTE
350
Selector Switch Switched to Position 5
350
Active Setting Group Retained
351
Power Loss
351
Settings Change
351
Settings Example 1
354
Settings Example 2
354
Settings Example 3
355
Timers Reset When Power Is Lost, Settings Are Changed, or Active Setting Group Is Changed
355
Output Contacts
356
Operation of Output Contacts for Different Output Contact Types
356
Output Contacts OUT101 through OUT107
356
Settings Example
356
ALARM Output Contact
357
Rotating Default Display
358
Circuit Breaker Status Indication
359
Reclosing Relay Status Indication
359
Traditional Indicating Panel Lights
359
Traditional Indicating Panel Lights Replaced with Rotating Default Display
359
General Operation of Rotating Default Display Settings
360
Reclosing Relay Status Indication
360
Settings Examples
360
Circuit Breaker Closed
361
Circuit Breaker Status Indication
361
Reclosing Relay Disabled
361
Reclosing Relay Enabled
361
Additional Settings Examples
362
Circuit Breaker Closed
362
Circuit Breaker Open
362
Display Only One Message
362
Active Setting Group Switching Considerations
363
Continually Display a Message
363
Reclosing Relay Disabled
364
Reclosing Relay Enabled
364
Switch to Setting Group 4 as the Active Setting Group
364
Additional Rotating Default Display Example
365
Trip and Close Circuits, Breaker Status, and SF6 Gas Pressure
365
Section 8: Breaker/Recloser Monitor, Battery/System Monitor, Metering, and Load Profile
369
Section 8: Breaker/Recloser Monitor, Battery
371
System Monitor, Metering, and Load Profile
371
Introduction
371
Breaker/Recloser Contact Wear Monitor
371
Breaker Monitor Setting Example
374
Breaker Maintenance Curve Details
376
Operation of SEL OGIC ® Control Equation Breaker Monitor Initiation Setting BKMON
378
0% to 10% Breaker Wear
379
10% to 25% Breaker Wear
379
25% to 50% Breaker Wear
379
Breaker Monitor Operation Example
379
50% to 100% Breaker Wear
381
Breaker Monitor Output
381
Example Applications
381
Via Serial Port
381
View or Reset Breaker Monitor Information - Including Trip Operation Counters
381
Determination of Control Initiated Trips and Externally Initiated Trips
382
Via Front Panel
382
Additional Example
383
Factory Default Setting Example
383
Battery System Monitor
384
Battery System Operation
385
SEL-351P Puts Itself "To Sleep
385
Battery System Diagnostics
386
Keep 12 VDC on While SEL-351P Is "Asleep
386
Wake Up" the SEL-351P
386
Automatic Battery Load Test
387
Battery Load Test Via Front Panel
387
Battery Load Test Via Serial Port
388
Additional Application
389
Battery Status
389
Metering
390
Comparison of Thermal and Rolling Demand Meters
391
Demand Metering
391
Thermal Demand Meter Response (EDEM = THM)
392
Rolling Demand Meter Response (EDEM = ROL)
393
Time = 0 Minutes
394
Time = 5 Minutes
394
Demand Meter Settings
395
Time = 10 Minutes
395
Time = 15 Minutes
395
Demand Current Logic Output Application - Raise Pickup for Unbalance Current
397
Residual Ground Demand Current below Pickup GDEMP
398
Residual Ground Demand Current Goes above Pickup GDEMP
398
Residual Ground Demand Current Goes below Pickup GDEMP Again
398
Demand Metering Updating and Storage
399
Energy Metering
399
Via Front Panel
399
Via Serial Port
399
View or Reset Demand Metering Information
399
View or Reset Energy Metering Information
399
Energy Metering Updating and Storage
400
Maximum/Minimum Metering
400
Via Front Panel
400
Via Serial Port
400
View or Reset Maximum/Minimum Metering Information
400
Maximum/Minimum Metering Updating and Storage
401
Load Profile Report (Only Available in Firmware Versions 1 and Greater)
402
Clearing the Load Profile Buffer
404
Determining the Size of the Load Profile Buffer
404
Section 10: Serial Port Communications and Commands/Section 10: Serial Port Communications and Commands
483
Section 10: Serial Port Communications and Commands
485
Serial Port Default Settings (for All Ports)
485
Wake-Up Port Default Settings
485
IRIG-B Time Code
486
SEL-351P Recloser Control to Computer
487
SEL-351P Recloser Control to Modem
488
SEL-351P Recloser Control to SEL-PRTU
489
Communications Protocol
490
Hardware Protocol
490
Software Protocols
490
SEL ASCII Protocol
491
Distributed Network Protocol (DNP) V3.00
492
SEL Compressed ASCII Protocol
492
SEL Distributed Port Switch Protocol (LMD)
492
SEL Fast Meter Protocol
492
Access Level 0
493
Access Level 1
493
Access Level E (EZ)
496
Access Level 0 Commands
498
ACC, EZA, BAC, and 2AC Commands (Go to Access Level 1, E, B, or 2)
498
Password Requirements and Default Passwords
498
Access Level Attempt (Password Not Required)
499
Access Level Attempt (Password Required)
499
BRE a Command (Breaker Monitor Data)
500
COMM Command (Communication Data)
501
DAT Command (View/Change Date)
502
EVE Command (Event Reports)
502
GRO Command (Display Active Setting Group Number)
502
HIS Command (Event Summaries/History)
503
IRI Command (Synchronize to IRIG-B Time Code)
504
LDP Command (Load Profile Report)
505
MET Command (Metering Data)
505
MET K - Instantaneous Metering
506
MET D - Demand Metering
507
MET E - Energy Metering
508
MET M - Maximum/Minimum Metering
509
QUI Command (Quit Access Level)
509
SER Command (Sequential Events Recorder Report)
510
SHO Command (Show/View Settings)
510
STA Command (Recloser Control Self-Test Status)
518
STA Command Row and Column Definitions
519
TAR Command (Display Relay Word Bit Status)
520
TIM Command (View/Change Time)
522
TRI Command (Trigger Event Report)
523
Access Level E (EZ) Commands
523
BTT Command (Battery Test)
523
SET EZ and SET FZ Commands (Change EZ Settings)
524
Access Level B Commands
525
BRE N Command (Preload/Reset Breaker Wear)
525
CLO Command (Close Breaker)
527
GRO N Command (Change Active Setting Group)
527
OPE Command (Open Breaker)
528
PUL Command (Pulse Output Contact)
529
Access Level 2 Commands
529
CON Command (Control Remote Bit)
529
COP M N Command (Copy Setting Group)
530
LOO Command (Loop Back)
530
PAS Command (View/Change Passwords)
530
SET Command (Change Settings)
531
STA C Command (Status Clear Command)
532
VER Command (Show Version Information)
532
SEL-351P Recloser Control Command Summary
535
Section 13: Testing and Troubleshooting
586
Introduction
588
Section 13: Testing and Troubleshooting
588
Testing Philosophy
588
Acceptance Testing
588
Commissioning Testing
588
Maintenance Testing
589
Testing Methods and Tools
590
Test Features Provided by the SEL-351P
590
Test Methods
590
Testing Via Front-Panel Indicators
591
Testing Via Output Contacts
591
Testing Via Sequential Events Recorder
591
SEL-351P Self-Tests
592
SEL-351P Troubleshooting
595
Inspection Procedure
595
Troubleshooting Procedure
595
All Front-Panel Leds Dark
595
Cannot See Characters on LCD Screen
595
SEL-351P Does Not Respond to Commands from Device Connected to Serial Port
595
SEL-351P Does Not Respond to Faults
596
Calibration
596
Factory Assistance
596
Appendix I: Mirrored Bits
600
Configuration
650
Overview
650
Data Access Method
651
Data-Link Operation
651
Device Profile
652
Object Table
654
Data Map
658
Relay Summary Event Data
661
Point Remapping
662
Appendix I: Mirrored Bits
666
Overview
666
Operation
666
Message Decoding and Integrity Checks
666
Message Transmission
666
Synchronization
667
Channel Monitoring
668
Loop-Back Testing
668
Mirrored Bits
668
Settings
669
Advertisement
Advertisement
Related Products
Schweitzer Engineering SEL-2032
Schweitzer Engineering SEL-300G
Schweitzer Engineering SEL-387-0
Schweitzer Engineering SEL-387-5
Schweitzer Engineering SEL-387-6
Schweitzer Engineering SEL-3355-2
Schweitzer Engineering Categories
Relays
Computer Hardware
Industrial PC
Controller
More Schweitzer Engineering Manuals
Login
Sign In
OR
Sign in with Facebook
Sign in with Google
Upload manual
Upload from disk
Upload from URL