Flash Adaptation Without Outdoor Sensor (Based On Room Temperature) - Samson TROVIS 5500 Mounting And Operating Instructions

Automation system and heating and district heating controller
Table of Contents

Advertisement

Functions
Room sensor
Flash adaptation
Parameters
Day set point
Night set point
6.10.1 Flash adaptation without outdoor sensor (based on room
temperature)
The flow temperature control starts with 'Day set point' for flow in rated operation or with
'Night set point' for flow in reduced operation as no set points calculated using characteris-
tics exist without an outdoor sensor. The 'Cycle time' determines the intervals at which the
flow temperature set point is corrected by 1 °C. The heating is then always switched off as
soon as the room temperature exceeds the 'Day set point' or 'Night set point' by 2 °C. Heat-
ing first starts again when the room has cooled off and the room temperature is 1 °C above
the set point. A 'KP (gain)' set to a value other than 0 causes a direct increase/decrease in
flow temperature set point when a sudden deviation in room temperature arises. A 'KP
(gain)' setting of 10.0 is recommended.
Functions
Room sensor
Outdoor sensor
Flash adaptation
Parameters
Day set point
Night set point
Parameters
Flow set point (day)
Flow set point (night)
EB 5573-1 EN
WE
Configuration
0
CO1, 2 > F01 - 1
0
CO1, 2 > F09 - 1
20 min
Cycle time: 0 to 100 min
0.0
KP (gain): 0.0 to 25.0
WE
Switch position: value range
20.0 °C
: –5.0 to 150.0 °C
15,0 °C
: –5.0 to 150.0 °C
WE
Configuration
0
CO1, 2 > F01 - 1
CO1 > F02 - 0
0
CO1, 2 > F09 - 1
20 min
Cycle time: 1 to 100 min
0.0
KP (gain): 0.0 to 25.0
WE
Switch position: value range
20.0 °C
: –5.0 to 150.0 °C
15,0 °C
: –5.0 to 150.0 °C
WE
Parameters: value range
50.0 °C
PA1, 2 > P03: –5.0 to 150.0 °C
30.0 °C
PA1, 2 > P04: –5.0 to 150.0 °C
Functions of the heating circuit
83