Test Run - Toshiba MMW-AP0271LQ-E Installation Manual

Hot water module (multi type)
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

2
Each time
button is pushed, hot
water module numbers in the control group
change cyclically. Select the hot water
module to change settings for.
The LED on the P.C. board of the selected hot
water module flashes. The hot water module for
change settings can be confirmed.
Hot Water Module P.C. board
LED
Flashing
3
Specify CODE No. [
] with "TEMP."
buttons.
4
Select SET DATA [
] with "TIME"
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another hot water module,
2
repeat from Procedure
.
• To change other settings of the selected hot
water module, repeat from Procedure
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
2
Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the hot
water module enters the normal stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
47-EN
 Group control
In a group control, a remote controller can control up to
maximum 8 units.
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "Electrical
Connection" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the hot water modules by connecting the
remote controller wires from the remote controller
terminal blocks (A, B) of the hot water module
connected with a remote controller to the remote
controller terminal blocks (A, B) of the other hot
water modules. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
/
 Remote controller sensor
/
CAUTION
Remote controller sensor can not
be used for the hot water module.
Remote controller sensor has no
3
function when remote controller
.
is connected to the hot water
module.
11

Test run

 Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistance
of 1 MΩ or more exists between the terminal
block L to N and the earth (grounding).
If resistance of less than 1 MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
• Do not press the electromagnetic contactor to
forcibly perform a test run. (This is very dangerous
because the protective device does not work.)
• Before starting a test run, set addresses by following
the Installation Manual supplied with the outdoor
unit.
 Execute a test run
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner's Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for
cases other than the test run
because it applies an excessive
load to the devices.
– 24 –
2, 4
3
1,5
1
Push
button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
2
Push
button.
3
Select the operation mode with
button, [
Heat].
• Can not select the hot water module in a mode
other than [
Heat].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
4
After the test run, push
button to
stop a test run.
1
(Display part is same as procedure
.)
5
Push
check button to cancel (release
from) the test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
48-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmw-ap0561lq-e

Table of Contents