Applicable Controls - Toshiba MMW-AP0271LQ-E Installation Manual

Hot water module (multi type)
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

▼ Output function wire
CAUTION
Output signal functions are separated from primary basic insulation.
• To prevent noise trouble, use 2-core shield wire.
• Determine the wire length between the hot water module output signal function terminal block and the relay up
to 2 m.
• Locally procure and install protective devices such as the heater and pump.
 Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
45-EN
– 23 –
10

Applicable controls

REQUIREMENT
When the hot water module is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on
the outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed.
Setup takes up to 10 minutes (usually about 5
minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes)
for the outdoor unit to start operating after the power
has been turned on.
Before the hot water module was shipped from the factory, all
units are set to [STANDARD] (factory default). If necessary,
change the indoor unit (including hot water module) settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a
wireless remote controller, simple remote controller
or group control remote controller by itself so install
a wired remote controller separately as well.
 Basic procedure for changing
settings
Change the settings while the hot water module is not
working. (Stop the hot water module before making
settings.)
CAUTION
Set only the CODE No. shown in
the following table: Do NOT set
any other CODE No.
If a CODE No. not listed is set, it
may not be possible to operate
the hot water module or other
trouble with the product may
result.
1
3
4
6
1
5
2
1
Push and hold
button and "TEMP."
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
• If the CODE No. is not [01], push
button to
clear the display content, and repeat the
procedure from the beginning. (No operation of
the remote controller is accepted for a while
after
button is pushed.)
(While hot water modules are operated under
the group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor unit (including hot
water module) model.)
46-EN