Toshiba MMW-AP0271LQ-E Installation Manual page 14

Hot water module (multi type)
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

 External dimensions
4-14×12
Long hole
33.5
400
33.5
Anchor bolt hole pitch
16
435
16
467
80
15
18
1.5
25.5
62.5
25-EN
(Unit: mm)
Refrigerant pipe
174
76
connecting port
Ø15.9 Gas side
R1-1/4 (PT1-1/4Screw)
3-Ø26
Water Outlet
Power supply
wiring port
Control wiring port
External signal
wiring port
19
R1-1/4(PT1-1/4Screw)
Refrigerant pipe
65
Water Inlet
connecting port
50
73
Ø9.5 Liquid side
R1 (PT1 Screw) Drain
– 13 –
 Fixing the hot water module
to floor
WARNING
• Be sure to install the hot
water module in a place able
to bear its weight.
If strength is insufficient, the unit
may fall down resulting in
human injury.
• Perform specified installation
work to protect earthquakes.
If the hot water module is
imperfectly installed, an
accident by falling or dropping
may be caused.
CAUTION
• Drain water is discharged from
the hot water module.
(Especially while operating)
Install the hot water module in a
place with good drainage.
• For installation, be careful of the
strength and level of the
foundation so that abnormal
sounds (vibration or noise) are
not generated.
• Be sure to install the hot water module in a place
strong enough to withstand its weight. If the base is
unstable, reinforce with a concrete base.
• The hot water module must be anchored on a level
surface. Use a level to check after installation.
• If the hot water module is installed near a room
where noise is a problem, using an anti-vibration
stand on the base of the unit is recommended.
1. Fix the hot water module with M8 anchor bolts at 4
positions. 20 mm projection is appropriate for an
anchor bolt.
(Unit: mm)
M8 anchor bolt 4 positions/unit
• Anchor bolt positions are as shown below:
(Unit: mm)
14×12 long hole
435
26-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmw-ap0561lq-e

Table of Contents