Condensate Piping - Dunkirk DKVLT-050 Installation, Operation & Maintenance Manual

Wall mounted gas boiler
Table of Contents

Advertisement

FIGURE 6-1 Condensate Drain
Condensate Tee
(fi eld installed)
on condensate drain
6 - COMBUSTION AIR AND VENT PIPING
pipe
Use materials acceptable to authority having jurisdiction.
In absence of such authority:
PVC or CPVC per ASTM D1785/D2845 Cement or
primer per ASME D2564 or F493.
Attach PVC tee provided with boiler and fi eld sourced
piping to condensate drain at bottom of boiler. See
Figure 6-1.
Slope condensate drain pipe minimum 1/4" per foot
(21mm/m) away from boiler.
Use fi eld source condensate pump if boiler located
below disposal point.
Field source condensate neutralizing kit as required
by authority having jurisdiction or for environmentally
friendly condensate disposal.