FITZROY FREESTANDING WOODBURNER
A. Yunca recommends that competent trades persons carry out all installations (e.g. NZHHA
Registered Installer), to obtain maximum performance and safe, efficient heating.
B. A permit is required and we suggest you check with local building inspectors as by-laws do
vary from area to area.
Also notify your Insurance Company that a solid fuel heater has been installed.
C. Floor Protector –
1. Must extend a minimum of 300mm in front of the door aperture.
2. Must extend at least 100mm from each side of the heater.
3. Ash Floor Protector must be constructed of non-combustible materials, with a
minimum thickness of 12mm
D. Seismic restraint – Heater must be restrained from seismic movement as required by NZS
7421. 10mm diameter bolting holes in the feet of the HOBSON allow restraint.
E. Manufacturers' recommended tested minimum clearances from combustible walls:
Tested to AS/NZS 2918 : 2001 by APPLIED RESEARCH SERVICES
Rear Clearance – from rear of top lip
Side Clearance (with YUNCA flue mounted shield fitted)
Corner Clearance (with YUNCA flue mounted shield fitted)
F. YUNCA Flue Kit (Tested to AS/NZS 2918:2001 Appendix F): Fig A, B & E
1. 4.2m x 150mm stainless steel flue
2. 2.4m x 250mm galvanised liner.
3. 1 x ceiling tile.
Please Note: All joints must be sealed with flue sealing compound. Use stainless steel
screws or rivets to join the flue pipe (three equally spaced places at each joint). The first
length of flue pipe must be screwed to flue spigot. The required minimum flue termination
height is 4.6 m above the floor protector.
G. FITZROY Flue Mounted Shield (Flue Guard) Kit (Tested to AS/NZS 2918:2001): Fig A
1 x 1200mm length lined back guard plus an adjustable 900mm extension.
1 x 1200mm length perforated front guard
1 x 1200mm length tertiary back guard with spacer tabs.
1 x Top front deflector shield (half round shape, angled when installed). Optional.
Please Note: The minimum Flue Mounted Shield height Is 1200mm. Extension accessory
shields are also available.
A division of Terry Young Ltd , New Zealand
INSTALLATION INSTRUCTIONS for
TESTED in compliance with AS/NZS 2918: 2001
- N.B. clearance from rear panel is 120mm
APRIL 2007
(with YUNCA flue mounted shield fitted)
4. 1 x insulation boundary shield.
5. 3 x spider brackets.
6. 1 x weather cap & cowl.
Clearance
100 mm
300 mm
130 mm
Page 1 of 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the FITZROY and is the answer not in the manual?

Questions and answers

Carol cottle
May 15, 2025

Blockage within fire bx

1 comments:
Mr. Anderson
May 22, 2025

To address a blockage in the Yunca Heating FITZROY firebox:

1. Remove the back and rear castings periodically, as ash can build up behind them and cause pressure on other parts.
2. Ensure the firebox is emptied of all bricks to provide room to maneuver parts.
3. When replacing the frame, remove bricks and any air tube from inside the frame first.
4. Remove the side bricks to enable the frame to be taken out of the firebox.

These steps help clear ash and debris that may be causing the blockage.

This answer is automatically generated

Subscribe to Our Youtube Channel

Summary of Contents for Yunca Heating FITZROY

  • Page 1 The required minimum flue termination height is 4.6 m above the floor protector. G. FITZROY Flue Mounted Shield (Flue Guard) Kit (Tested to AS/NZS 2918:2001): Fig A 1 x 1200mm length lined back guard plus an adjustable 900mm extension.
  • Page 2 FITZROY – TYPICAL FLUE INSTALLATION (not drawn to scale) FIG A FIG B TOP CAP (Fits inside flue) ENLARGEMENT OF CEILING ASSEMBLY 5mm Max 25mm min. BETWEEN LINER & ANY TIMBER LINER POSITIONED BY SPIDER BRACKETS. TOP/BOTTOM FLUE LINER POSITIONED BY SPIDER BRACKETS.
  • Page 3 FIG C: HEATER DIMENSIONS – Fitzroy (Drawings on this page not drawn to scale) Ash Floor Protector FIG D: HEATER POSITION. * N.B. Measurement “A” is taken from the top lip at the rear of the fire. Above: Non combustible wall clearances. Brick lining from floor to within 25mm of ceiling.
  • Page 4: Important Information

    E. Cracked and broken components e.g. glass panels or fire bricks, may render the installation unsafe. IF THE A WATERBOOSTER IS FITTED: Note: A water booster cannot be fitted to the Sub 1.0 Clean Air model Fitzroy A. Do not connect to an unvented hot water system B.