Table 10: Radii of Coiled Expansion Loops and Developed Lengths of Expansion Offsets
Anticipated Linear
Expansion (LE) (inch-
es)
R
1
1/2
L
2
R
1
1
L
2
R
1
1-1/2
L
2
R
1
2
L
2
R
1
2-1/2
L
2
R
1
3
L
2
R
1
3-1/2
L
2
R
1
4
L
2
Pipe Bends
When bending soft copper, use long radius bends. Refer to the "Radii of Coiled Expansion Loops and Developed Lengths of Expansion
Offsets" table for minimum radius specifications, as shown above.
In-line Refrigeration Components
Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee fittings, and other after-market accessories are not permitted
on the refrigerant piping system between the outdoor unit and the indoor unit.
Duct Free Single Zone systems are provided with redundant systems that assure oil is properly returned to the compressor. Sight-glasses
and solenoid valves may cause vapor to form in the liquid stream.
Over time, dryers may deteriorate and introduce debris into the system. The designer and installer should verify the refrigerant piping system is free of
traps, sagging pipes, sight glasses, filter dryers, etc.
Field-provided Isolation Ball Valves
LG allows the installation of field-supplied ball valves with Schrader ports at each indoor unit. Full-port isolation ball valves with Schrader
ports (positioned between valve and indoor unit) rated for use with R410A refrigerant should be used on both the liquid and vapor lines.
If valves are not installed and a single indoor unit needs to be removed or repaired, the entire system must be shut down and evacuated.
Position valves with a minimum distance of three (3) to six (6) inches of pipe on either side of the valve, and placed between six (6) and
twelve (12) inches from the run-out pipe to the upstream main pipe. If ball valves are installed closer to the indoor unit, a section of pipe
becomes a dead zone when the valves are closed where oil may accumulate.
GENERAL INSTALLATION GUIDELINES
Nominal Tube Size (OD) inches
1/4
3/8
6
7
38
44
9
10
54
63
11
12
66
77
12
14
77
89
14
16
86
99
15
17
94
109
16
19
102
117
17
20
109
126
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Piping Materials and Handling
1/2
3/4
8
9
50
59
11
13
70
83
14
16
86
101
16
19
99
117
18
21
111
131
19
23
122
143
21
25
131
155
22
26
140
166
27