Pump Down Operation; Forced Operation - Daikin 3MXS40K3V1B2 Installation Manual

R410a split series
Table of Contents

Advertisement

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop
valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a
hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop
forced cooling operation.
1.

Forced operation

1) Turn the Operation Mode switch (SW2) to "COOL".
2) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop
forced cooling.
11
Gas stop valve
Liquid stop valve
Service PC-board
Operation Mode
switch (SW2)
Close
Hexagonal
wrench
Valve caps
Forced Operation
switch (SW1)
nEnglish

Advertisement

Table of Contents
loading

This manual is also suitable for:

3amx52e4v1b23mxs52e4v1b2

Table of Contents