Power source

PV037/PV057 is equipped with DC24V input power. If the supply power is other than
DC24V, whatever less or excess, it will severely damage the HMI. Therefore, check
the switching power supply supporting the DC power regularly.
To avoid electronic shock, be sure the Power Cable is unplugged from the power
outlet when connecting the cable to the HMI.

Grounding

From the FG terminal at the rear side of HMI, please make sure the grounding is
made exclusively.
When the FG terminal is connect, be sure the wire is grounded. Without grounding,
the operation of HMI may be severely affected by excess external noise levels and
vibrations.
Use a cable at 2 m㎡ (AWG 14) to ground the equipment. Ground resistance must
be less than 100Ω(class3).Note that the ground cable must not be connected to the
same ground point as the power circuit.
Installation
Mount the HMI from the front of a suitable preserved hole.
Attached the brackets behind.
Fasten the screw of the brackets with proper force. Tightening too much may cause
damage to the structure of the unit.
Input and Output signal lines must be separated from the power cables for
operational circuits. Use shielded cables or it may cause unpredictable problems.
Do not allow cut wires, filling, or shavings to fall inside a unit or block when drilling
holes or connecting cables/lines.

Environment

Do not install in areas subject to excessive dust, oily mist, conductive dust, corrosive
gas, or flammable gas.
Do not mount in areas subject to shock or vibration.
Do not mount in areas subject to high temperature, moisture, or rain.
Indicated loss of life, severe personal injury, or substantial property damage will result
if proper precautions are not taken.