STANDARD WALL-MOUNTED INDOOR UNITS
Installation and Best Layout Practices
Wired Controller Connections
Figure 112:Wired Controller Connection on the Indoor Unit Terminal
Block—LSN090HSV4 and LSN120HSV4 models.
Indoor Unit Terminal Block
GND
1(L1 ) 2(L2)
To Outdoor Unit or Branch Distribution Unit
(Multi F MAX Systems Only)
Figure 115:Wired Controller Connection on the Indoor Unit Terminal
Block—LMN077HVT and LMN157HVT models.
Indoor Unit Terminal Block
GND
1(L1 ) 2(L2)
3(C)
To Outdoor Unit or Branch Distribution Unit
(Multi F MAX Systems Only)
Wired Controller Placement
Wired controllers include a sensor to detect room temperature. To maintain comfort
levels in the conditioned space, the wired controller must be installed in a location away
from direct sunlight, high humidity, and where it could be directly exposed to cold air.
Controller must be installed four (4) to five (5) feet above the floor where its LED display
can be read easily, in an area with good air circulation, and where it can detect an aver-
age room temperature.
Do not install the wired controller near or in:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Radiant heat from the sun or appliances
• Concealed pipes and chimneys
• An area where temperatures are uncontrolled, such as an outside wall
86 | STD. WALL-MOUNTED
CN-REMO
3
To Wired Controller
CN-REMO
To Wired Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 113:Wired Controller Connection on the Indoor Unit Terminal
Block—LSN180HSV4 models.
Indoor Unit Terminal Block
GND
1(L1 ) 2(L2)
To Outdoor Unit or Branch Distribution Unit
(Multi F MAX Systems Only)
Figure 116:Wired Controller Connection on the Indoor Unit Terminal
Block—LMN247HVT models.
Indoor Unit Terminal Block
GND
1(L1 ) 2(L2)
To Outdoor Unit or Branch Distribution Unit
(Multi F MAX Systems Only)
Figure 114:Proper Location for the Wired Controller.
TEMP
ot e
Cont
roller
Rem
NO
F
MULTI
F
MULTI
MAX
CN-REMO
3
To Wired Controller
CN-REMO
3
4
To Wired Controller
YES
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
NO
4 to 5 feet
above the floor