Heating Capacity Table - LG MULTI F Engineering Manual

Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
Table 33: Multi F Standard Wall-Mounted Indoor Units Heating Capacity Table.
Outdoor Air Temp.
Model No. /
Nominal Capacity of
°F DB
Indoor Unit (Btu/h)
0
5
10
17
20
25
30
LMN077HVT
35
7,000
40
45
47
50
55
60
63
68
0
5
10
17
20
25
30
LSN090HSV4
35
9,000
40
45
47
50
55
60
63
68
0
5
10
17
20
25
30
LSN120HSV4
35
12,000
40
45
47
50
55
60
63
68
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor
units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
STANDARD WALL-MOUNTED INDOOR UNITS
61
°F WB
TC
-0.4
4.17
4.5
4.70
9
5.22
15
5.93
19
6.19
23
6.63
28
7.01
32
7.40
36
7.74
41
8.08
43
8.22
46
8.35
51
8.57
56
8.57
59
8.57
64
8.57
-0.4
5.35
4.5
6.03
9
6.71
15
7.61
19
7.95
23
8.52
28
9.01
32
9.50
36
9.94
41
10.37
43
10.55
46
10.72
51
11.00
56
11.00
59
11.00
64
11.00
-0.4
7.10
4.5
8.00
9
8.90
15
10.10
19
10.55
23
11.30
28
11.95
32
12.60
36
13.18
41
13.77
43
14.00
46
14.23
51
14.60
56
14.60
59
14.60
64
14.60
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Indoor Air Temp. °F DB
64
68
TC
TC
4.11
4.07
4.64
4.60
5.17
5.13
5.87
5.83
6.13
6.09
6.57
6.53
6.96
6.92
7.34
7.30
7.68
7.64
8.02
7.98
8.16
8.12
8.29
8.25
8.51
8.47
8.51
8.47
8.51
8.47
8.51
8.47
5.28
5.23
5.95
5.90
6.63
6.58
7.54
7.49
7.88
7.83
8.44
8.39
8.93
8.88
9.42
9.37
9.86
9.81
10.30
10.25
10.48
10.43
10.64
10.59
10.93
10.88
10.93
10.88
10.93
10.88
10.93
10.88
7.00
6.93
7.90
7.83
8.80
8.73
10.00
9.93
10.45
10.38
11.20
11.13
11.85
11.78
12.50
12.43
13.08
13.02
13.67
13.60
13.90
13.83
14.13
14.06
14.50
14.43
14.50
14.43
14.50
14.43
14.50
14.43
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Heating Capacity Table

70
72
TC
TC
4.05
3.99
4.58
4.52
5.11
5.05
5.75
5.81
6.08
6.02
6.52
6.46
6.90
6.84
7.28
7.22
7.62
7.56
7.96
7.90
8.04
8.10
8.23
8.17
8.45
8.39
8.45
8.39
8.45
8.39
8.45
8.39
5.20
5.12
5.88
5.80
6.56
6.48
7.39
7.46
7.80
7.72
8.37
8.29
8.86
8.78
9.34
9.27
9.78
9.71
10.22
10.15
10.32
10.40
10.57
10.49
10.85
10.78
10.85
10.78
10.85
10.78
10.85
10.78
6.90
6.80
7.80
7.70
8.70
8.60
9.80
9.90
10.35
10.25
11.10
11.00
11.75
11.65
12.40
12.30
12.98
12.88
13.57
13.47
13.80
13.70
14.03
13.93
14.40
14.30
14.40
14.30
14.40
14.30
14.40
14.30
STD. WALL-MOUNTED | 67
75
TC
3.82
4.34
4.87
5.56
5.81
6.22
6.63
7.04
7.39
7.73
7.87
7.98
8.16
8.20
8.22
8.25
4.90
5.58
6.26
7.14
7.46
7.99
8.52
9.04
9.48
9.92
10.10
10.24
10.48
10.52
10.55
10.60
6.50
7.40
8.30
9.48
9.90
10.60
11.30
12.00
12.58
13.17
13.40
13.59
13.90
13.96
14.00
14.06

Hide quick links: