Installation of hanging bolt
• Consider the piping / wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer
to the external view.
• When a ceiling already exists, lay the drain pipe,
refrigerant pipe, control wires, and remote controller
wires to their connection locations before hanging
the indoor unit.
Procure hanging bolts washer and nuts for installing
the indoor unit (these are not supplied).
Hanging bolt
M10 or W3/8
4 pieces
Nut
M10 or W3/8
12 pieces
Washer
M10
8 pieces
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Rubber
Anchor bolt
(Slide type
(Blade type
(Pipe hanging
bracket)
bracket)
anchor bolt)
Steel flame structure
Use existing angles or install new support angles.
Hanging bolt
Hanging bolt
Support angle
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
13-EN
Installation Manual

Installation of indoor unit

Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the M10 flat washers to the
hanging bolt.
• Put washers at up and down of the hanging bracket
of the indoor unit to hang down the indoor unit.
• Check that four sides are horizontal with a level
gauge. (Horizontal degree: Within 5 mm)
Hanging bolt
M10 flat washer
(W3/8 or M10)
Nut
(W3/8 or M10)
M10 flat washer
Nut
(W3/8 or M10)
REQUIREMENT
• Hang the unit in a horizontal position.
When unit is hanged to slant, it may cause overflow of
drainage.
• Install the unit within the dimension according to the
figure below.
• Using level vial or vinyl hose to confirm whether the
unit is hang horizontally.
Front view
Side view
Water pouring
Vinyl hose
Set the air intake and
Set the drain pipe
connecting port side
air discharge sides are
within 5 mm with each
within 5 mm lower than
opposite side.
other.
SMMS Concealed Duct High Static Pressure Type
– 7 –
Diagrams for making connecting flanges
The connecting flange (Incl. the fixing screw) is not supplied to the indoor unit. When the connecting flange is
necessary, produce them in locally.
Drawing figure is as follows. (Material: Galvanized steel plate, thickness of 1.6 mm)
<Air discharge port flange>
65
250
25
<Air intake port connecting flange>
65
250
25
Installation Manual
1130
250
250
250
65
1080
25
10-Ø8 hole
1130
250
250
250
65
1080
25
10-Ø8 hole
(Unit: mm)
14-EN