  • Page 1 Va po r m ist ® E le c t r i c Hu mi di f i e r Ins tallatio n, Op eration and Main tenan ce Man u al...
  • Page 2 Dripping water can cause property damage; bacteria and mold growth can cause illness. Supply water pressure greater than 80 psi (550 kPa) can cause the humidifier to overflow. Page ii • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 3: Table Of Contents

    Two-year limited warranty . . . . . . . . . . . . . . . . . . . . . .Back cover DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 1...
  • Page 4: Product Overview

    DI/RO water . Vapormist-DI models can be converted in the field for use with potable or softened water . Contact your DRI-STEEM® representative or distributor for parts and instructions . Page 2 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 5 Ultra-sorb dispersion ® Space Distribution Unit (SDU) shown mounted directly above a Vapormist humidifier OM-55-1 Figure 3-4: OM-636-1 SDU mounted remotely Figure 3-2: Rapid-sorb dispersion ® OM-56-1 OM-637-1 DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 3...
  • Page 6: Electrical Specifications, Capacities And Weights

    ** For wire sizing, the highest leg draw is shown due to current imbalance. † Add the following to Vapormist weights if using an SDU option (these weights are for additional control components housed within the Vapormist cabinet): – SDU-I: 12 lbs (5.5 kg) –...
  • Page 7: Dimensions

    0.63" 2.25" (57 mm) 0.75" (19 mm) (16 mm) Power wire knockout 1.50" (38 mm) 5.75" (146 mm) 24.2" Control wiring knockout DC-1167 (614 mm) DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 5...
  • Page 8: Choosing A Location For The Humidifier

    . Choosing a location for the dispersion control devices See Figure 13-1 for recommended installation locations for the dispersion assembly and associated control devices . Page 6 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 9: Mounting The Humidifier

    To dispersion assembly Right side electrical Secured to controls: 36" (915 mm) supporting wall Supporting wall Left side: 12" (305 mm) Front 36" (915 mm) Floor: 24" (610 mm) DC-1201 DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 7...
  • Page 10: Supply Water And Drain Piping

    • Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet. • Dashed lines indicate provided by installer. • The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required; however, governing codes prevail. • Install a union in the water supply and drain lines as shown to allow tank removal. • Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty. • See the next page for recommended piping for Vapormist-DI models (models that use DI/RO water). • See the dispersion section of this manual for more information about piping that connects the humidifier to the dispersion assembly. Page 8 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 11 • Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet. • Dashed lines indicate provided by installer. • The water supply inlet is more than 1" (25 mm) above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required; however, governing codes prevail. • Install a union in the water supply and drain lines as shown to allow tank removal. • Damage caused by chloride corrosion is not covered by our DRI-STEEM warranty. • See the previous page for recommended piping for Vapormist standard water models. • See the dispersion section of this manual for more information about piping that connects the humidifier to the dispersion assembly. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 9...
  • Page 12 For other Drane-kooler mounting options or for more information, contact your DRI-STEEM representative/ distributor, or view the Drane-kooler product data sheet in the literature section at www.dristeem.com Page 10 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 13: Wiring

    . Connect the drain wire to the shield/screen ground terminal with wire less than 2" (50 mm) in length . • Do not ground shield at the device end. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 11...
  • Page 14 • Do not use chassis or safety grounds as current- carrying commons. Never use a safety ground as a conductor or neutral to return circuit current. Page 12 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 15: Humidistat And Transmitter Placement

    Relief air Return air Air handling unit Wall or Vapor absorption has taken place Window partition Point of vapor absorption Humidifier dispersion assembly Turning vanes Doorway Window DC-1084M mc_060508_0750 DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 13...
  • Page 16: Dispersion

    While obtaining documents from our web site or from Dri-calc is the quickest way to review our literature, we'd also be happy to mail to you any literature you need. Page 14 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 17: Interconnecting Piping Requirements

    • Steam supply adapters are available from DRI-STEEM. These adapters convert a tubing outlet on the humidifier to threaded pipe, allowing a pipe connection . • 90° elbows are not recommended; use two 45° elbows, 1' (0.3 m) apart . • Thin wall tubing heats up faster and causes less start-up loss than heavy wall pipe . More on the next page ▶ DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 15...
  • Page 18 *** To minimize loss of capacity and efficiency, insulate tubing and piping. † Developed length equals measured length plus 50% of measured length, to account for pipe fittings. Page 16 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 19: Drip Tee Installation

    Open funnel or floor drain. DC-1450 See first note below. Notes: • Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature. • Support vapor hose so there are no sags or low spots. • Dashed lines indicate provided by installer. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 17...
  • Page 20: Sdu-I And Sdu-E

    Vapormist Both SDUs can be mounted on a wall directly above the Vapormist cabinet or mounted on a wall remote from the Vapormist . Use the mounting template on the box for correct placement . Two lag bolts are provided with each fan unit .
  • Page 21 24" Note: The SDU-E dispersion box requires an installed condensate drain line (610 mm) and water seal, provided by installer. See Page 20. DC-1078 OM-282-7 DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 19...
  • Page 22 P-trap piping, rated for 212 °F (100 °C) Spill funnel. Plumb to floor drain. Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements. OM-1245 Page 20 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 23 Minimum non-wetting height above the steam outlet of the SDU-E Throw: Minimum non-wetting horizontal distance from the steam outlet of the SDU-E. Spread: Minimum non-wetting width from the steam outlet of the SDU-E. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 21...
  • Page 24: Single Tube

    . For multiple injury. tube assemblies, see information on Rapid-sorb on pages 24-30 . Page 22 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 25 . hot. Discharged steam is not visible. Contact • See the Hose Kit Sizing table on the previous page. with hot surfaces or air into which steam has been discharged can cause severe personal injury. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 23...
  • Page 26: Rapid-Sorb

    Rapid-sorb header either inside or outside the duct . See the Dri-calc Installation Guides library or contact your representative/distributor or DRI-STEEM for installation instructions for air handler or vertical airflow applications . Page 24 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 27: Operation

    1½" (DN40) Vapor hose toward 2" (DN50) 1/8"/ft (1%) Rapid-sorb 2"/ft toward Vertical toward condensate 1/8"/ft (1%) header 1½" (DN40) drain Tubing or pipe toward 2" (DN50) Rapid-sorb DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 25...
  • Page 28: Operation

    DO NOT use a petroleum-based lubricant . 4 . Position the flange of the L-bracket so it is upstream of the tubes when the assembly is raised and fastened into position . Page 26 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 29: Operation

    • L-bracket to duct • Dispersion tubes to L-bracket • Hose clamps on 2" (DN50) tubes 9 . Secure and seal the dispersion tube escutcheon plate and condensate drain tube escutcheon plate around the respective tubes, if applicable . DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 27...
  • Page 30: Operation

    . • When installing slip couplings for 1½" (DN40) dispersion tubes, take care not to shear the O-rings . • Set the slip coupling on the header stub or dispersion tube so the O-ring is resting on the face of the tubing . More on next page ▶ Page 28 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 31: Operation

    9 . Secure and seal the header escutcheon plate around the header . 10 . See the next page for steam supply and condensate drain line connection instructions . DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 29...
  • Page 32: Operation

    . 4 . All drain lines must be installed and sized according to governing codes . Page 30 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 33: Start-Up Procedure

    (see the Vapor-logic3 Installation and Operation Manual) . However, at start-up, DRI-STEEM recommends initially running the humidifier with the factory default setting for skim time . DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 31...
  • Page 34: Standard Water Models Maintenance

    . The skim time is field adjustable using the Vapor-logic3 keypad . Each time the Vapormist refills, it fills to an elevation near the lip of the skim/overflow fitting . A portion of the refill water then flows to the drain carrying most of the minerals left by the previous evaporating cycle .
  • Page 35 DRI-STEEM warranty. – High limit switch – Airflow proving switch mc_021908_1410 – Low water level probe . Pull out probe plug; fill valve should energize . mc_060208_1005 More on the next page ▶ DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 33...
  • Page 36 . Inspect the composite plastic probe housing for any signs of cracking, roughness, or deterioration . If found, replace . mc_060208_1055-2 More on the next page ▶ Page 34 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 37 . 5 . Replace enclosure . 6 . Leave chamber dry, power off and the water shut-off valve closed until the next humidification season . DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 35...
  • Page 38: Di/Ro Water Models Maintenance

    I m p o r t a n t : not disconnect by pulling on cord or wires . • Disconnect the drain union on the back left corner of the frame . • Disconnect the steam supply hose from the top of the tank. • Lift the tank foot above the frame flange and slide the tank assembly forward to remove . mc_071408_1020-2 More on the next page ▶ Page 36 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 39 Vapor-logic3 manual . 5 . Replace enclosure . 6 . Leave chamber dry, power off, and water shut-off valve closed until the next humidification season . mc_060208_1420 DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 37...
  • Page 40: Replacement Parts

    R e p l a c e m e n t p a r t s Figure 38-1: Humidifier replacement parts Vapormist standard water model Vapormist-DI water model Note: Refer to the table on the next page for replacement part numbers. OM-768 Page 38 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 41 Cover, tank gasket, VM99 6-34 160695-002 Tube weld, low water, long, VMDI 6-34 167788 Washer, No. 8 external tooth, pltd 700200-003 Notes: * Specify humidifier model and serial numbers when ordering. • Contact your DRI-STEEM representative to order parts. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 39...
  • Page 42 Cap, black 409593-002 Dispersion chamber for SDU with 1½" outlet 160445-003 Dispersion chamber for SDU with 2" outlet 160445-004 Notes: * This is an assembly of multiple parts. • Contact your DRI-STEEM representative to order parts. Page 40 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 43 Screw, 8-32 × 1½" PHMS Phillips 700170-007 Nut retainer, 8-32 409593-001 Cap, black 409593-002 Tubelet, 0.375" × 0.375" molded 310280-006 Notes: * This is an assembly of multiple parts. • Contact your DRI-STEEM representative to order parts. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 41...
  • Page 44 SSR, 480 V, 60 Amp, 1-pole 408677-005 Contactor, 60 A 407001-021 Notes: Refer to model for correct selection and quantity. ** Substitute Vapor-logic3 version number for “x.x.x” • Contact your DRI-STEEM representative to order parts. Page 42 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 45 408999-001 Channel, wire cover 12.5" 408999-002 Channel, wire 12.5" 408999-001 Notes: Refer to model for correct selection and quantity. ** Substitute Vapor-logic3 version number for “x.x.x” • Contact your DRI-STEEM representative to order parts. DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 43...
  • Page 46 N o t e s Page 44 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...
  • Page 47 N o t e s DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual • Page 45...
  • Page 48: Two-Year Limited Warranty

    DRI-STEEM, and paid for in full by the purchaser . © 2009 DRI-STEEM Corporation mc_051308_0630 Form No. VM-IOM-0509 Printed on 30% Part No. 890000-201 Rev E recycled paper Page 46 • DRI-STEEM Vapormist Electric Humidifier Installation, Operation, and Maintenance Manual...