U-Line 1224R User Manual page 42

1000 series 24" solid door refrigerator
Hide thumbs Also See for 1224R:
Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE •
REFRIGERATION SYSTEM DIAGNOSIS GUIDE
System
Suction
Condition
Pressure
Normal
Normal
Overcharge
Higher than
normal
Undercharge
Lower than
normal
Partial
Somewhat
Restriction
lower than
normal -
in vacuum
Complete
In deep
Restriction
vacuum
No Gas
0 PSIG to 25"
ERRORS
*All errors are logged in memory.
*Only door error is displayed on the display and has an
audible signal.
*For clear ice models, pump error is displayed via alert
light with no audible alerts.
E1:Thermistor 1 open.
E2:Thermistor 2 open (Does not apply to this model).
E3:Thermistor 3 open (Does not apply to this model).
E4:Thermistor 4 open (Does not apply to this model).
E5:Thermistor 1 shorted.
E6:Thermistor 2 shorted (Does not apply to this model).
E7:Thermistor 3 shorted (Does not apply to this model).
E8:Thermistor 4 shorted (Does not apply to this model).
E9:Door open error.
Pi:Pump Circuit open (Does not apply to this model).
Suction
Compressor
Line
Discharge
Slightly below room
Very hot
temperature
Very cold -
Slightly warm
may frost heavily
to hot
Warm -
Hot
near room
temperature
Warm -
Very hot
near room
temperature
Room temperature
Room
(cool)
temperature
(cool)
Room temperature
Cool to hot
(cool)
Condenser
Capillary
Tube
Very hot
Warm
Hot to warm
Cool
Warm
Warm
Top passes
Room
warm lower
temperature
passes cool
(cool) or colder
(near room
temperature
due to liquid
Room
Room
temperature
temperature
(cool)
(cool)
Room
Room
temperature
temperature
(cool)
(cool)
MAIN CONTROL
The main control board is very robust and is rarely the
cause of system issues. It is important to fully diagnose
the board for any suspected failures before attempting to
remove the board for replacement or service. Follow the
guidelines below to fully test and diagnose the main
control.
Power Fault
If the unit does not (or seems to not) power on, follow the
flow chart below to help diagnose the issue. Before
beginning it is important to first verify the unit is not
simply set to sabbath mode.
u-line.com
SERVICE
Evaporator
Wattage
Cold
Normal
Cold
Higher than
normal
Extremely cold
Lower than
near inlet -
normal
outlet below
room
temperature
Extremely cold
Lower than
near inlet -
normal
outlet below
room
temperature
backing up
No refrigeration Lower than
normal
No refrigeration Lower than
normal
Troubleshooting - Extended 2