Please Read Before Proceeding - Lochinvar KNIGHT WH 55 - 399 User's Information Manual

Lochinvar boiler user manual
Table of Contents

Advertisement

Please read before proceeding

The Knight Wall Mount Installation and
NOTICE
Operation Manual along with the Knight
Wall Mount Service Manual are for use
only by a qualified heating installer/service
technician.
Information Manual for your reference.
Improper
alteration, service or maintenance can
cause property damage, personal injury
(exposure to hazardous materials) or loss
of life. Installation and service must be
performed by a qualified installer, service
agency or the gas supplier (who must
read and follow the supplied instruction
before installing, servicing, or removing
this boiler. This boiler contains materials
that have been identified as carcinogenic,
or possibly carcinogenic, to humans).
When calling or writing about the boiler
NOTICE
– Please have the boiler model and serial
number from the boiler rating plate.
Consider piping and installation when
determining boiler location.
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by the
consignee.
Factory warranty (shipped with unit) does
not apply to units improperly installed or
improperly operated.
Failure to adhere to the guidelines on this
WARNING
page can result in severe personal injury,
death, or substantial property damage.
Refer only to this User's
installation,
adjustment,
User's Information Manual
Boiler service and maintenance –
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
• To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to
the boiler. This boiler is equipped with a control which
will automatically shut down the boiler should air or
vent be blocked.
If vent or air blockage is easily
accessible and removable, remove it. The boiler should
attempt to restart. If blockage is not obvious or cannot
be removed, have the boiler and system checked by a
qualified service technician.
• Should overheating occur or gas supply fail to shut off,
do not turn off or disconnect electrical supply to the
circulator. Instead, shut off the gas supply at a location
external to the appliance.
• Do not use this boiler if any part has been under water.
The possible damage to a flooded appliance can be
extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
Boiler water –
• Thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency
heat exchanger can be damaged by build-up or
corrosion due to sediment.
• Do not use petroleum-based cleaning or sealing
compounds in the boiler system. Gaskets and seals in
the system may be damaged.
substantial property damage.
• Do not use "homemade cures" or "boiler patent
medicines". Serious damage to the boiler, personnel,
and/or property may result.
• Continual fresh make-up water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat
transfer, overheats the stainless steel heat exchanger,
and causes failure. Addition of oxygen carried in by
makeup water can cause internal corrosion. Leaks in
boiler or piping must be repaired at once to prevent
makeup water.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are specifically
formulated for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used in hydronic
systems.
This can result in
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Knight wh 55-399

Table of Contents