Troubleshooting
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
The unit has failed to prove main burner
ignition after four (4) attempts.
Flame Fail Ign
(cont'd)
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART SYSTEM
display to reset.)
Flame Sequence
(will require a manual
reset once the condition
The flame detector circuit is seeing a flame
has been corrected.
signal while no flame is present.
Press the RESET button
on the SMART SYSTEM
display to reset.)
(continued)
DESCRIPTION
Service Manual
CORRECTIVE ACTION
• Verify that the plastic hose from the gas valve to the air
inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are correctly
installed and that there are no obstructions.
• Check for 24 vac to the gas valve at the 2-pin
connection on the side of the main control board during
the ignition attempt. If no voltage is present, replace
the main control board.
• If 24 vac is present at the main control board, check
the wiring between the main control board and the gas
valve.
Replace the wiring if necessary.
disconnect the wiring from the gas valve and attempt to
measure voltage at that point. The main control board
can detect if the gas valve is not connected and will
display the Gas Valve or Gas Valve Fail fault.
• If 24 vac is present, check the outlet of the valve to
ensure the valve is flowing gas. With a manometer
connected to the outlet tap of the gas valve, when the
unit is in the prepurge period, there should be a
negative pressure present.
energized a change in pressure should occur. If the
pressure change does not occur, the gas valve is not
opening. Replace the gas valve.
• Inspect
flame
sensor
Reference page 31 of this manual for removal and
cleaning procedures. Replace if necessary.
• Inspect and clean the heat exchanger as necessary.
Reference page 32 of this manual for cleaning
procedures.
• Inspect the burner. Reference page 31 of this manual
for removal and cleaning procedures.
necessary.
• Replace the main control board.
• Check supply voltage for proper polarity.
• Check external wiring for voltage feedback.
• Check the flame rod and make sure it is clean.
• Check the internal wiring for bad connections.
• Replace main control board.
Do not
When the valve is
and
associated
wiring.
Replace if
39