Trouble Shooting Guide - BONAIRE Slimline Owner's Manual

Multi-appliance control for ducted gas central heating ducted evaporative air conditioning
Table of Contents

Advertisement

Multi-Appliance Slimline Control
Ducted Evaporative Air Conditioning

TROUBLE SHOOTING GUIDE

PROBLEM
Unit fails to start
Pump fails to start
Water leaking
Water Droplets in
air stream
Excessive humidity
Inadequate Cooling
Unpleasant Odor
Rapid formation of
white deposits on
pads
THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.
FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE REFER
Bonaire Control Systems
PROBABLE CAUSE
A
Black – out
b
Tripped Circuit Breaker
c
Blown Fuse
d
Electrical Fault
a
Pump Seized
b
Pump Burnt Out
a
Float Valve Leaking
b
Drain from Celdek Pads
a
Loose Delivery Tube
b
Break in tubing
c
Pump Delivers Excessive Water to
Pads
a
Inadequate Relief
b
Outside humidity high
a
Dirty Filters
b
Dry Filters
c
Dialflo not set correctly
a
Unit located near odor source
b
New Celdek filter smell
High Mineral Content
TO THE LAST PAGE OF THESE INSTRUCTION
REMEDY
a
Wait
b
Reset
c
Replace
d
Call Climate Technologies
Service Provider
a
Isolate power and then take off
top of pump and try to free it.
Some lubricant may help.
b
Call Climate Technologies
Service Provider
a
Check adjustment or replace seal
b
Normal Operation
a
Check and tighten
b
Replace as necessary
c
Adjust the Dialflo to reduce the
flow
a
Provide more open area to
relieve stale air
b
Turn pump off.
a
Clean / Replace
b
Check water delivery system.
Adjust if necessary.
c
Adjust Dialflo so that the pads
have even saturation.
a
Remove source
b
Smell will disappear after a period
of operation (Approximately 48
hours or use).
Bleed off should be set at
maximum. More regular
maintenance may be required.