12.1.2 Cooling Operation
12.1.2.1
Thermostat control
• Compressor is OFF when Intake Air Temperature – Internal Setting Temperature < -1.5℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature – Internal Setting Temperature >
Compressor OFF point +0.5K.
12.1.3 Soft Dry Operation
12.1.3.1
Thermostat control
• Compressor is OFF when Intake Air Temperature – Internal Setting Temperature < -2.5℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature – Internal Setting Temperature >
Compressor OFF point +0.5K.
12.1.4 Heating operation
12.1.4.1
Thermostat control
• Compressor is OFF when Intake Air Temperature – Internal Setting Temperature > +2.0℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature – Internal Setting Temperature<
Compressor OFF point -0.5K.