LOCATION
FURNACE
SIDES
SUPPLY PLENUM WITHIN 6 ft. OF FURNACE
BACK
FURNACE
FURNACE OR PLENUM
TOP
HORIZONTAL WARM AIR DUCT WITHIN 6 ft. OF FURNACE
BOTTOM
FURNACE (COMBUSTIBLE FLOOR WITH THE SUB-BASE †)
HORIZONTALLY OR BELOW FLUE PIPE
FLUE PIPE
VERTICALLY ABOVE FLUE PIPE
FRONT
FURNACE
Figure 12 : Model CVM Size 120
Table 11 : Minimum clearances to combustible materials
APPLICATION
† When used with floor base model: *KLASB0601DET or **KLASB0701DET
UPFLOW
Ø
2.54 cm (1")
Ø
5.08 cm (2")
5.08 cm (2")
Ø
10.16 cm (4")
22.86 cm (9")
20.32 cm (8")
20
DOWNFLOW
HORIZONTAL
5.08 cm (2")
5.08 cm (2")
5.08 cm (2")
2.54 cm (1")
2.54 cm (1")
Ø
5.08 cm (2")
5.08 cm (2")
5.08 cm (2")
7.62 cm (3")
* Ø
** Ø
10.16 cm (4")
10.16 cm (4")
22.86 cm (9")
22.86 cm (9")
20.32 cm (8")
60.96 cm (24")