Download Print this page

Installing The Ups; Connecting The Internal Battery - HP T1000J Quick Start Card

Advertisement

This symbol indicates that you should not discard waste
electrical or electronic equipment (WEEE) in the trash.
For proper disposal, contact your local recycling/reuse
or hazardous waste center.

Connecting the Internal Battery

To ensure proper battery operation, connect the internal battery.
1.
Verify that the UPS power is off and unplugged.
2.
Remove the UPS front bezel.
3.
Slide up and remove the metal battery cover.
NOTE: For HP T750 G2, HP T750J, and HP T1000 G3
models, carefully remove the metal battery cover to avoid
damaging the battery disconnect blades.
HP T750 G2,
HP T750J, and
HP T1000 G3
4.
Remove the protective label from the internal battery connector.
5.
Connect the red wire to the positive (+) battery connector.
NOTE: A small amount of arcing may occur when
connecting the batteries. This is normal and does not
damage the unit or present any safety concern.
6.
Replace the metal battery cover.
HP T1000J,
HP T1500 G3, and
HP T1500J
7.
Replace the UPS front bezel.

Installing the UPS

To install the UPS:
1.
If you are installing HP Power Manager software, first connect
your computer to the USB port or UPS communication port
using the supplied cable.
2.
For 230V models only. Plug the detachable power cord into the
input connector on the UPS rear panel.
3.
Plug the UPS power cord into a power outlet.
Verify that the circuit has an upstream overcurrent protection of
15A for 100–120V models or 10A for 230V models.
4.
Plug the equipment to be protected into the UPS output
receptacles.
NOTE: DO NOT connect laser printers to the UPS
because of the exceptionally high power requirements of
the heating elements.
Figure 1 Typical UPS Installation (120V model shown)
5.
Press and hold the On/Off button until you hear the UPS
beep. The
(Power On) indicator illuminates indicating that
power is available to the connected equipment. The UPS
conducts a self-test and enters Normal mode.
If the UPS beeps or a UPS alarm indicator stays on, refer to the
UPS user guide.
NOTE: The batteries charge to 90% capacity in
approximately 3 hours. However, to fully charge, HP
recommends that the batteries charge for 6 to 24 hours
after installation or long-term storage.