Table 12—Gas Rate (cu ft/hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
REVOLUTION
Cu Ft
Cu Ft
Cu Ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
Table 13—Speed Selector
COLOR
Black
Yellow (When Present)
Blue
Red
White
started. See thermostat manufacturer's instructions for adjusting
heat anticipator and for varying heating cycle length.
Step 5—Check Safety Controls
This section covers the safety controls that must be checked before
the installation is complete.
SIZE OF TEST DIAL
SECONDS
FOR 1
5
1
2
REVOLUTION
Cu Ft
Cu Ft
50
72
144
51
71
141
52
69
138
53
68
136
54
67
133
55
65
131
56
64
129
57
63
126
58
62
124
59
61
122
60
60
120
62
58
116
64
56
112
66
54
109
68
53
106
70
51
103
72
50
100
74
48
97
76
47
95
78
46
92
80
45
90
82
44
88
84
43
86
86
42
84
88
41
82
90
40
80
92
39
78
94
38
76
96
38
75
98
37
74
100
36
72
102
35
71
104
35
69
106
34
68
108
33
67
110
33
65
112
32
64
116
31
62
120
30
60
124
29
58
FACTORY-
SPEED
SHIPPED
CONNECTION
High
Cool
Medium High
Spare
Medium Low
Heat
Low
Spare
Common
C
OM
5
Cu Ft
360
355
346
340
333
327
321
316
310
305
300
290
EXAMPLE: 5.0 AMPS ON AMMETER
281
10 TURNS AROUND JAWS
273
265
Fig. 60—Amp Draw Check with Ammeter
257
CHECK PRIMARY LIMIT CONTROL
250
243
This control shuts off combustion control system and energizes
237
air-circulating blower motor if furnace overheats. Recommended
231
method of checking this limit control is to gradually block off
225
return air after furnace has been operating for a period of at least
220
5 minutes. As soon as limit control has shut off burners, return-air
214
opening should be unblocked to permit normal air circulation. By
209
using this method to check limit control, it can be established that
205
limit is functioning properly and operates if there is a restricted
200
return-air supply or motor failure. If limit control does not function
196
during this test, cause must be determined and corrected.
192
CHECK PRESSURE SWITCH
188
This control proves operation of draft inducer. Check switch
184
operation as follows:
180
178
1. Turn off 115-v power to furnace.
173
2. Remove main furnace door and disconnect inducer motor lead
170
wires from wire harness.
167
3. Turn on 115-v power to furnace.
164
4. Set thermostat to call for heat and wait 1 minute. When
161
pressure switch is functioning properly, hot surface ignitor
155
should NOT glow, and control center diagnostic light flashes
150
a Status Code 31. If hot surface ignitor glows when inducer
145
motor is disconnected, shut furnace down immediately. De-
termine reason pressure switch did not function properly and
correct condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor leads, reinstall main furnace door,
and turn on 115-v power supply.
Step 6—Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify manual reset switch has continuity.
3. Verify that blower and control access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer's instruc-
tions.
6. Review User's Guide with owner.
7. Leave literature packet near furnace.
46
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT
TERMINAL BLOCK
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201