13

FUNCTION SETTING

13-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
<Table 1> Function selections
Function
Power failure
Not available
automatic recovery
Available
Indoor temperature
Average data from each indoor unit
detecting
Data from the indoor unit with remote controllers
Data from main remote controller
LOSSNAY
Not supported
Supported (indoor unit dose not intake outdoor air through LOSSNAY)
connectivity
Supported (indoor unit intakes outdoor air through LOSSNAY)
Power supply
230V
voltage
208V
Auto mode
Auto energy-saving operation ON
(only for PUZ)
Auto energy-saving operation OFF
2: [36˚F] (Normal)
Frost prevention
3: [37˚F]
temperature
Humidifier control
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Change of
Standard
For high humidity
defrosting control
Meaning of "Function setting"
mode02:indoor temperature detecting
No indoor temperature(ta)=
No1. Average data of the
sensor on all the
indoor units
No2. the data of the sensor
on the indoor unit that
connected
with remote controller
No3. the data of the sensor
on main remote
controller
Settings
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
initial
ta=(A+B)/2
setting
ta=A
ta=C
Mode No. Setting No.
1
01
2
1
02
2
3
1
03
2
3
1
04
2
1
05
2
1
15
2
1
16
2
1
17
2
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
ta=(A+B)/2
ta=B
ta=C
84
: Initial setting
Remarks
(when sent from the factory)
The setting is
applied to all
the units in the
same
refrigerant
system.
OUTDOOR
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
REMOTE
(MAIN)
(SUB)
(MAIN)
ta=A
ta=A
ta=A
ta=A
ta=C
ta=C