No.
Part name
T
Horizontal louver
U
Evaporator
(Heat exchanger)
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Procedures
1) Remove shaft of the horizontal louver
from the back body.
(First remove the left shaft, and then
remove other shafts while sliding the
horizontal louver leftward.)
1) Follow to the procedure in the item
2) Remove the pipe holder from the rear side of the main unit.
3) Remove two fixing screws at the left side of the end plate of the heat
exchanger.
4) Remove the heat exchanger fixing
holder by removing the two fixing
screws used to secure it.
5) Remove right side of the end plate
from two fixing ribs while sliding
slightly the heat exchanger rightward.