7.4.

Filter Change

All filters in the air handling unit (inc. cooling module) are
monitored by the unit's filter monitoring system. The filters
must be replaced when the monitoring system indicates a
filter change, but at least annually. Filter monitoring can be
adapted to local conditions using Airlinq Service Tool. The
filters are tested automatically daily at 12 noon (time can
be set using "Airlinq Service Tool").
NB: When changing filters, the unit must be switched
off (press function button for at least 2 seconds),
disconnected from the mains and prevented from
being switched on.
NB: The control system filter monitoring must be reset
after a filter change.
7.4.1.

Reset Service

Airlinq Viva:
Reset filter change alarm by pressing and holding the holiday
mode button and function button simultaneously for 10
seconds. The unit will then automatically start, the control
panel will flash a short amber warning symbol followed by
a short red alarm symbol. The filter alarm is now reset. The
filter change alarm can also be reset using a PC running
Airlinq User Tool or Airlinq Service Tool connected to the
control panel.
Airlinq Orbit:
Reset the filter alarm under control panel menu "Settings
- Reset Service" or using a PC running Airlinq Service Tool.
This will also reset the filter alarm. The filter change alarm
can also be reset using a PC running Airlinq User Tool or
Airlinq Service Tool connected to the control panel.
Press "Confirm" to reset service or "Cancel" to cancel the
reset.
Units with no control panel:
The filter change alarm must be reset using a PC running
Airlinq User Tool or Airlinq Service Tool. This will also reset
the filter alarm. Use the USB port direct on the control unit
for PC connection or connect a control panel and use the
USB port on the panel.
7.4.2.

Cooling Module Filter Change

NB: When changing filters, the unit must be switched
off (press function button for at least 2 seconds),
disconnected from the mains and prevented from
being switched on.
• Carefully open the base plate while it is supported.
NB: Open the side of the wall frame first. The base
plate is heavy.
• Slacken the retaining plate (certain models only)
and pull out the old filter on the fresh air side of
the holder.
• Clean the inside of the cooling module and supply air
duct, check component condition and cleanliness.
Clean the components if necessary.
• Insert a new filter with the correct direction of flow
in the filter holder. (The arrow on the side of new
M5/F7 filters shows flow direction. The arrow must
point into the unit) and and fit the retaining plate
(certain models only).
• Close the base plate, lock covers.
• Replace the exhaust air filter on the air handling
unit. See sect. "Filter Change for CV80-200, DV
1000, AML100-800 and AMP300-800" on page 29
Filter position:
or
28