OPERATING PROCEDURE
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
( 10 ) Remove the compressor.
NOTE
Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
2
(0 MPa).
Photo 6
Discharge pipe
Glass
terminal
Compressor
Compressor
set nuts
31
PHOTOS
Suction pipe
Terminal cover