<Thermistor Characteristic graph>
•Room temperature thermistor (TH1)
Thermistor for
•Pipe temperature thermistor/liquid (TH2)
lower temperature
•Condenser/evaporator temperature
Thermistor R
=15k' ± 3%
0
Fixed number of B=3480 ± 2%
1
Rt=15exp { 3480(
273+t
0:
15k'
10:
9.6k'
20:
6.3k'
25:
5.2k'
30:
4.3k'
40:
3.0k'
Thermistor for
drain sensor
Thermistor R
=6.0k' ±5%
0
Fixed number of B=3390 ± 2%
1
Rt=6exp { 3390(
273+t
0:
6.0k'
10:
3.9k'
20:
2.6k'
25:
2.2k'
30:
1.8k'
40:
1.3k'
60:
0.6k'