Pair Number Setting
3
• This is the setting to specify the unit to operate with the wireless remote controller.
• Make setting for J41, J42 (Jumper wire) of indoor controller board and the pair number of wireless remote cotroller.
• The pair number setting is available with the 4 patterns as shown in the following table. Make setting for the pair number
(J41, J42) of indoor controller board and the pair number of wireless remote controller which is used
as shown in the following table. *The initial setting is Pair No. "0".
Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.

MODEL SELECT

min
Press the
button twice continuously. Pair No. "0" blinks.
Press the temp
Press the SET button with something sharp at the end.
Set pair number is lighted for 3 seconds then turned off.
Pair No. of wireless remote controller Indoor PC board
0
1
2
3 ~ 9
4
Test Run
TEST
RUN
SWING
NOT AVAILABLE
ON/OFF
TEMP
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK
LOUVER
h
TEST RUN
min
SET
RESET
CLOCK
E-132
button to set the pair number you want to set.
Initial setting
Cut J41
Cut J42
Cut J41, J42
CN90
* The positions of the connectors may be
different according to the model.
Please refer to the wiring diagram to
confirm the positions of the connectors.
Jumper wire (J41, J42)
Measure an impedance between the power supply terminal block on the outdoor unit
and the ground with a 500V Megger and check that it is equal to or greater than 1.0 M .
Turn on the main power to the unit.
TEST RUN
Press the
button twice continuously.
(Start this operation from the status of remote controller display turned off.)
and current operation mode are displayed.
TEST RUN
MODE
Press the
(
cool air is blown out from the unit.
MODE
Press the
(
warm air is blown out from the unit.
FAN
Press the
button and check whether strong air is blown out from the unit.
VANE
Press the
button and check whether the auto vane operates properly.
Press the ON/OFF button to stop the test run.
NOTE : • Point the remote controller towards the indoor unit receiver
while following steps
• It is not possible to run in FAN, DRY or AUTO mode.
for Ceiling Suspended models
MODE
CHECK LOUVER
TEST RUN
) button to activate COOL
) button to activate HEAT
to
.
PAR-SL94B-E
MODEL SELECT
ON/OFF
TEMP
FAN
AUTO STOP
VANE
AUTO START
h
min
SET
RESET
CLOCK
mode, then check whether