Freestyle FS-80 NG Instruction Manual page 30

Wall mount gas-fired central heating water boilers
Hide thumbs Also See for FS-80 NG:
Table of Contents

Advertisement

W
FreeStyle
ALL
13 DIRECT VENT —
1.
a. Cut a clearance hole to clear the termination outside
diameter as prescribed in the kit instructions.
b. Insert a galvanized metal thimble in the vent pipe hole.
2.
3.
termination outside diameter.
1.
terminations, on page 31.
2.
3.
penetration as shown in Figure 34 or per concentric kit
instructions.
The supports/bracing used must support the termina-
tion assembly to prevent vertical slippage or sideways
movement.
must not cut into the pipe or contain sharp edges that
The vent and air piping must be securely sup-
ported, and must not rest its weight on the boiler
fittings. DO NOT drill or screw into either the
vent pipe or air pipe. Failure to properly support
the vent and air piping could result in vent pip-
ing damage, resulting in possible severe personal
injury, death or substantial property damage.
When inserting the partially-assembled termi-
the boiler will not operate. Once the rain cap
has been cemented to the assembly, there is
no way to correct the problem. The assembly
removed and cleaned. Altering the assembly in
any way could result in severe personal injury
or death due to toxic flue product emissions.
a PVC concentric vent attachment.
Do not connect any other appliance to the vent
pipe or multiple boilers to a common vent pipe.
4.
and all supports have been attached, install a bird screen
a.
Figure 35, page 31
pylene kits.
b. Cement the rain cap in place.
30
M
-
OUNT GAS
FIRED WATER BOILER
See notices on previous page.
Figure 34.
Boiler Manual
(continued)
Figure 33
Figure 34
-
-
Part number 550-142-850/0115