Liebert AccuVar Installation, Operation And Maintenance Manual page 11

Liebert surge protection nstallation, operation and maintenance manual
Table of Contents

Advertisement

7.
An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit
breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below
(also indicated on the "Dimensional Information" pages in this manual). The SPD shall be connected in accordance with all
national and local electrical codes.
5. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground)
marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical
distribution system, keep all conductors as short as possible and avoid sharp bends.
and a Neutral connection is not available, please contact factory.
TVSS
Model #
Series
SI016 – SI025
SI032 – SI050
Interceptor II
SI060 – SI075
SI100
Hxxxxx111 (250kA)
Hxxxxx222 (320kA)
Hybrid Advantage
Hxxxxx333 (400kA)
Hxxxxx444 (750kA)
Type SS Series
All Units
LM060 – LM080
LM Series
LM100 – LM150
LM200 – LM250
AccuVar
All Units
LPM 100-2
PowerSure LPM
LPM 160
PowerSure LPL
N/A
Surge Voltage Ratings. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated,
in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August
15, 1996, marked on this product, the suggested wire size must be utilized to connect the unit to your facilities power grid.
Connections made with conductors other than the size provided may result in different SVRs.
6. Connection to Form 'C' contacts shall be with #18 – 22 AWG. The ratings of the Form 'C' contacts are 5 amps at 250 VAC
maximum with a power factor of 1.0. For additional information on Interceptor II connections, see page 15.
7. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are
illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure that power is applied to the SPD.
If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection
at 1-800-288-6169 or 1-607-724-2484.
8. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is
illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
9. The protection modules in these SPDs may be replaceable, contact Liebert/Emerson Network Power Surge Protection for
replacement. (Note: ACV, LPM, & LPL units do not have replaceable modules).
Installation, Operation and Maintenance Manual
If the SPD model is a Wye confi gured unit (4W+G),
Allowable Range
Circuit Breaker Size
With Disconnect Without Disconnect With Disconnect
15A – 150A
15A – 175 A
15A – 175A
15A – 175A
15A – 175A
15A – 150A
15A – 175A
15A – 175A
15A – 175A
15A – 175A
N/A
15A – 175A
15A – 150A
15A – 175A
15A – 100A
15A – 175A
N/A
15A – 30A
30 Amp
N/A
N/A
30 Amp or less
Connection Wire Size
Without Disconnect
#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
N/A
#14 – 1/O
#14 – #2
#14 – 2/O
#14 – 2/O
#14 – #10
N/A
N/A
N/A
N/A
N/A
9
Liebert TVSS Units SL-22085 Rev 2, 11/2006
Surge Suppression Systems
Factory Suggested Size
Circuit Breaker
Connection
Size
Wire Size
60 Amp
80 Amp
80 Amp
100 Amp
60 Amp
80 Amp
80 Amp
80 Amp
80 Amp
40 Amp
40 Amp
100 Amp
30 Amp
30 Amp
#12 Provided
#12 Provided
30 Amp Required
#6
#4
#4
#2
#6
#4
#4
#4
#4
#8
#8
#2
#10