[ IX Troubleshooting ]
1. Error Code
7100
Total capacity error
2. Error definition and error detection method
The model total of indoor units in the system with one outdoor unit exceeds limitations.
3. Error source, cause, check method and remedy,
Error source
Outdoor unit
(1)
The model total of indoor units in the sys-
tem with one outdoor unit exceeds the fol-
lowing table.
(2)
The model selection switches (SW5-1 - 5-
4) on the outdoor unit are set incorrectly.
(3)
The outdoor unit and the auxiliary unit
(OS) that is connected to the same system
are not properly connected.
HWE0804A
Cause
Capacity Total
Model
72 model
96
96 model
124
120 model
156
144 model
187
168 model
218
192 model
249
216 model
280
240 model
312
264 model
343
288 model
374
312 model
405
336 model
436
360 model
468
SW5
Model
1
2
3
4
72 model
OFF ON OFF OFF
96 model
ON
ON OFF OFF
120 model
OFF OFF ON
OFF
- 210 -
Check method and remedy
1)
Check the model total (capacity code total) of in-
door units connected.
2)
Check the model name (capacity code) of the
connected indoor unit set by the switch (SW2 on
indoor unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the model name (ca-
pacity code).
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-1 - 5-4 on
the outdoor unit control board).
Confirm that the TB3 on the OC and OS are
properly connected.
GB