Mitsubishi Electric PUHY-P72 Service Manual page 147

City multi
Hide thumbs Also See for PUHY-P72:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in opera-
unit
tion
Operating
Model
conditions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Outdoor
Accumulator outlet
unit
Temp. of
SCC outlet (TH6)
each sec-
tion
Compressor inlet
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
HWE0804A
PUHY-P72THMU-A
26.7°C/19.4°C [80°F/67°F]
DB/WB
Unit
-
m [ft]
-
kg
[lbs-oz]
A
V
Hz
52
Pulse
141
1400
2.78/0.90
MPa
[psi]
[403/131]
69 [156]
44 [111]
10 [50]
10 [50]
24 [75]
°C [°F]
17 [63]
47 [117]
23 [73]
10 [50]
- 138 -
Outdoor unit model
PUHY-P288TSHMU-A
PUHY-P96THMU-A
P120THMU-A
35°C/ - [95°F/ - ]
6
6
48/48/48/48/48/48
5 [16-3/8 ]
10 [32-3/4 ]
65 [213-1/4]
Hi
34 [75]
68.3
230
65
387/387/387/387/387/387
185
1400
2.78/0.90
[403/131]
74 [165]
46 [115]
10 [50]
10 [50]
26 [79]
14 [57]
38 [100]
25 [77]
10 [50]
PUHY-
74
185
1400
2.78/0.90
[403/131]
73 [163]
40 [104]
10 [50]
10 [50]
20 [68]
15 [59]
42 [108]
19 [66]
10 [50]