Technical Characteristics - Eaton 5S 700 Installation And User Manual

Hide thumbs Also See for 5S 700:
Table of Contents

Advertisement

Available languages

Available languages

Technical characteristics

Eaton 5S
• UPS power
• Nominal input voltage
• Input frequency
• V oltage/frequency of battery backup
outlets 19 in battery mode
• Total output current for all outlets
• O utput current of battery backup
outlets 19
• Leakage current
• Input protection
• Transfer time
• Telephone/Data surge protection
• Sealed lead-acid battery
• Automatic battery test
• Average battery life
• Operating temperature
• Storage temperature
• Operating relative humidity
• Operating elevation
• Safety standards
• E lectromagnetic compatibility
standards
• Dimensions (mm/inch)
• Weigth (kg/lb)
(*) Warning: Output cables should not exceed 10m (32.81 ft) length.
614-06818-01
700
700 VA /
420 W
50/60 Hz (46 - 70 Hz working range)
115 V +15 % -20 % (60 Hz ± 1 Hz)
10 A max
6.1 A max
10 A resettable circuit
breaker
12 V, 9 Ah
4 years typical, depending on temperature and number of discharge cycles
-25 °C to +55 °C / -13 °F to 131 °F
260 x 87 x 250 /
10.24 x 3.43 x 9.84
5.9 / 13.0
1000
1000 VA /
600 W
93 V - 138 V
15 A max
8.7 A max
0.4 mA
15 A resettable circuit breaker
5 ms typical
Tel, ISDN, ADSL, Ethernet
2 x 12 V, 7 Ah
Once a week
0 to 35 °C / 32 to 95 °F
0 to 85 %
0 to 2000 m / 0 to 6562 ft
UL 1778
FCC Part 15 Class B
382 x 87 x 250 / 15.04 x 3.43 x 9.84
9.7 / 21.4
1500
1500 VA /
900 W
13.1 A max
2 x 12 V, 9 Ah
11.6 / 25.6
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5s 10005s 1500

Table of Contents