Mitsubishi SRK52HE Technical Manual page 43

Wall mounted type room air conditioner
Table of Contents

Advertisement

(4) SUPER LINK ADAPTER (SC-AD-E)
(a) Functions
1)
Transmits the settings from the Super link option to the indoor units.
2)
Returns the priority indoor unit data in response to a data request from the Super link option.
3)
Inspects the error status of connected indoor units and transmits the inspection codes to the Super link option.
4)
A maximum of 16 units can be controlled (if in the same operation mode).
(b) Wiring connection diagram
SC-AD-E
Master/Slave address
Network address [00] ~ [47]
1)
Set the super link network address with SW1 (10-position) and SW2 (1-position).
2)
Without a remote control (no wired remote control and no wireless remote control), set SC-AD-E SW3-1 to ON
(Master).
Basic Connections
Internal/external Crossing
Blue
A
Blue
B
Red
X
White
Y
Black
Z
OFF
Outdoor unit
Indoor unit
X Y Z
SC-AD-E
Remote control
X Y Z
X Y Z
A B
Network
A B
options
Connection to super link
(total length of wires: 1000 m maximum)
0.75 ~ 2.0 mm
X
Y
Z
Connection to the terminal block for remote control (polar)
(total length of wires: 600 m maximum)
Master/Slave Address
SW 3-1
ON
Master
Slave
● Make sure to ground one side only of the shielding wire.
41
-
-
2
2-core
No.
Name ot the recommended signal wire
1
Shielding wire
2
Vinylcabtire round cord
3
Vinyl cabtire round cable
4
Control vinyl insulated, vinyl sheath cable
Shielding wires:
100 ~ 200 m ................. 0.5 mm
~ 300 m ................. 0.75 mm
~ 400 m ................. 1.25 mm
~ 600 m ................. 2.0 mm
× 3-core wires
2
× 3-core wires
2
× 3-core wires
2
× 3-core wires
2