Gx series modulating, direct vent, gas-fired condensing boilers natural or propane 150,000 to 399,000 btuh input (44 pages)
Summary of Contents for HydroTherm MultiPulse AM Series
Page 1
Attachment G Building 86 (Albert T. Summers Center) Charleston, WV AMP8-1203 ® AM SERIES PULSE BOILER TROUBLESHOOTING GUIDE FOR CERTIFIED CONTRACTORS ONLY 260 NORTH ELM STREET 5211 CREEKBANK ROAD WESTFIELD, MA 01085 MISSISSAUGA, ONTARIO L4W 1R3 CANADA (413) 568-9571 • FAX (413) 568-9613 (905) 625-2991 •...
SECTION 1: OPERATION BOILER OPERATING LIGHTS GC-4A On GC-4A ignition control - visible thru a AMBER Part of 115V ON-OFF rocker switch LIGHT cutout in control cover near the 6-pin LIGHT (SW1). Side of electric box (AM-100 and Molex connector. OFF when no 24V to AM-150).
Page 4
5. The ignition sequence (8 sec. duration) is controlled AUTOMATIC RESTART FEATURE: The GC-4A ignition by the module which provides a spark at the spark control is equipped with an automatic reset feature. If plug & energizes the gas valve (Green Light “ON). the control completes an ignition sequence (5 attempts The pre-purge blower continues to operate during for ignition) without sustaining or proving gas ignition,...
LIGHTING AND OPERATING INSTRUCTIONS (Honeywell VR-8305M Gas Valve) WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing properly damage, personal injury or loss of life. C. Use only your hand to turn gas control knob. Never A.
SECTION 2: TROUBLE SHOOTING CAUTION: Label all wires prior to disconnection 2. If the boiler is running, but exhibits one of the when servicing controls. Wiring errors can cause following conditions, observe the operating improper and dangerous operation. light conditions and use the procedure(s) under Verify proper operation after servicing.
CONDITION B GC-4A LIGHT OFF, RED LIGHT OFF, AMBER LIGHT ON Turn Rocker Switch OFF and ON. If, within 10 seconds, the GC-4A light comes ON proceed to “CONDITION “E”. Replace Red Light (if OFF). If GC- 4A light remains OFF, proceed with check. POSSIBLE CAUSE VERIFICATION SOLUTION...
Page 11
CONDITION C GC-4A LIGHT OFF, RED LIGHT ON Turn Rocker Switch OFF and ON. If, within 10 seconds, the GC-4A light come ON, proceed to CONDITION “E”. If after the toggle switch is turned “OFF” and “ON”: - GC-4A light remains “OFF”. - Red light is “ON”...
Page 12
CONDITION D GC-4A LIGHT ON (If Red or Amber lights are OFF, replace lamp or switch.) Boiler may be in an ignition seqence - wait 40 seconds for an attempt at ignition (Green Light ON). If there is no attempt at ignition: turn Rocker Switch on boiler OFF and ON. Observe and clock the time the GC-4A light is ON.
CONDITION E GC-4 LIGHT BLINKING Turn the Rocker Switch OFF and ON. Observe GC-4 light and clock ON time before it begins to blink. If Red or Amber Lights OFF, replace lamp or switch. If the boiler starts and runs, a temporary problem may have corrected itself, (I.E., low gas pressure or a blockage of the inlet, etc).
Page 14
CONDITION “E” continued… 2. If measured fan pressure is at or below the minimum for Fan Prove Switch (PS2) operation. POSSIBLE CAUSE VERIFICATION SOLUTION Fan Motor Turn Rocker Switch and Gas Valve If you read 115V, proceed with top knob OFF. Remove air cushion verification.
CONDITION “E” continued … POSSIBLE CAUSE VERIFICATION SOLUTION Wiring to GC-4A (115V) Turn Rocker Switch OFF. With an If no continuity on any wire, replace ohmmeter, check continuity of red & or repair as required. black wires of the 3-conductor Molex connector.
CONDITION #2 - BOILER ATTEMPTS IGNITION (8 SECONDS) WITH ONLY A “COUGH” OR NO IGNITION: THEN SHUTS OFF GC-4A Light is “ON”; Red Light “ON”; Green Light “ON”; - during each 8 sec. ignition trial (5 attempts). Unit does not run after 3 min. 45 sec. The GC-4 light then blinks. NOTE: ON A START-UP, BOILER MAY LOCK OUT SEVERAL TIMES BEFORE ALL AIR IS PURGED FROM GAS LINE.
Page 17
CONDITION #2 continued … POSSIBLE CAUSE VERIFICATION SOLUTION Ignition Lead Turn Rocker Switch “OFF.” Remove If no continuity or damaged lead - cover from ACC. Remove the fan then replace wire harness assembly. assembly on the AM-100 & -150. (See “Procedures” section). With an ohmmeter, check lead for Reseal “ACC”...
Page 18
CONDITION #2 continued..B. IF FAN PRESSURE MEASURES “ABOVE - NORMAL” CONDITIONS: +2.4" W.C. OR HIGHER ON AM-100 & -150 +1.6" W.C. OR HIGHER ON AM-300 POSSIBLE CAUSE VERIFICATION SOLUTION Blocked Condensate Drain Remove condensate drain tube at If condensate begins to flow rear base of boiler.
CONDITION #2 continued..C. IF FAN PRESSURE MEASURES “BELOW-NORMAL” CONDITIONS: • LESS THAN 1.45" W.C. ON AM-100 & -150 • LESS THAN 1.0" W.C. ON AM-300 POSSIBLE CAUSE VERIFICATION SOLUTION Air Inlet Pipes/Fan Assembly Turn “OFF” Rocker Switch. Turn gas If fan pressure increases to normal (AM-100 &...
Page 20
CONDITION 3A - BOILER SHORT CYCLES BUT AUTOMATICALLY RESTARTS POSSIBLE CAUSE VERIFICATION SOLUTION Recirculation of Exhaust Visually check air inlet terminal(s) for If there is recirculation, temporarily at Inlet Terminals exhaust recirculation (vapor path). extend exhaust vent. If this eliminates problem, proceed with NOTE: On thru-the-wall installations permanent fix.
Page 21
CONDITION #3A continued … POSSIBLE CAUSE VERIFICATION SOLUTION Overfire Reassemble boiler. Check input to If overfired-adjust input - see boiler using one of the prescribed “Procedures” Section. If obtaining methods under “Procedures” section rate is difficult or starts are adversely of the manual.
CONDITION 4 - BOILER AND CONDENSATE WATER LEAKS • WATER IN BASE PAN (AM-100 & -150) POSSIBLE CAUSE VERIFICATION SOLUTION Condensate Drain Fitting Check for moisture at bottom side If wet, remove tubing and fitting. and Tubing of fitting and tubing. Inspect and repair or replace as required.
Page 23
CONDITION #4 continued … • WATER ON FLOOR AT REAR OF BOILER (AM-300) POSSIBLE CAUSE VERIFICATION SOLUTION Condensate Fitting & Tubing Check condensate fitting & tubing. Tighten,or replace fitting/tubing. Flue Box Gasket Check for moisture at flue box If wet, replace gasket following attachment to rear plate on packaged instructions.
CONDITION 5 - BOILER NOISE - CONTROL AND ADJUSTMENTS A certain amount of operational noise is to be considered “NORMAL” when operating a PULSE BOILER. Most “objectionable” noise occurs on start-up and is correctable by the procedures outlined in this section. NORMAL OPERATION: START-UP CHARACTERISTICS: •...
CONDITION 5a - PROLONGED “STUTTER” ON START-UP (AM-300) • An occasional stutter when starting can be expected (i.e. - cold water/initial start-up.) POSSIBLE CAUSE VERIFICATION SOLUTION Incorrect Gas Supply Check Gas Supply Pressure and Adjust Gas Supply Pressure as Pressure (should be gas input rate as outlined under necessary.
CONDITION 5b - COMBUSTION / OPERATING NOISE (STEADY-STATE) POSSIBLE CAUSE VERIFICATION SOLUTION Boiler Overfired Check gas supply pressure and Adjust supply pressure and/or input gas input rate as described in rate as necessary. If boiler is in “Procedures” section of this operation more than 5 years - it is manual.
CONDITION 5c - VIBRATION NOISE (IN-HOUSE) BUT, REMOTE FROM BOILER (STEADY-STATE) POSSIBLE CAUSE VERIFICATION SOLUTION Air Intake & Exhaust Lines Visually check that the lines are If pipes are rigidly supported or in supported with vibration isolator direct contact with the building supports &...
CONDITION 5e - OBJECTIONABLE (LOCALIZED) NOISE - STEADY-STATE POSSIBLE CAUSE VERIFICATION SOLUTION Exhaust Line Leak Check exhaust vent line, joints & Repair or replace as necessary with connections to boiler. “SCH-40” CPVC parts. “O” Ring between Boiler & With the boiler running for 5-minutes; If a leak is suspect, remove lower Exhaust Cushion Chamber feel around the jacket about 3"...
SECTION 3: SERVICING & REPAIR PROCEDURES 2. Locate the plastic tube connecting the Fan Prove SERVICING TOOLS LIST: • Volt/OHM/Continuity Meter Pressure Switch (PS2) to the 3/16" barb tee on the boiler. Disconnect the plastic tubing from either • 15/16" Deep Socket •...
7. Turn the gas supply “OFF” at the up-stream 4. Turn Rocker Switch and Gas Valve top knob to service valve before replacing the line pressure ON. Approximately 30 seconds after combustion test plug on the combination gas valve. starts, manometer should read according to TABLE 1 below.
4. Apply a 1/4" wide bead of silicone at the edge and 5. Secure orifice in place with PVC cement. Replace completely around the 3-1/2" diameter hole in the fan assembly in boiler. Reassemble boiler lid and top of the flue box. Allow silicone to skim. panel and turn gas “ON”.
Page 32
GAS VALVE TOP KNOB EXTENDED REGULATOR ADJUSTMENT CAP GAS VALVE OUTLET PRESSURE TAP 1/8" OD TUBING GAS VALVE NOT SHOWN IN REGULATOR VENT OPENING MOUNTED POSITION FOR CLARITY PURPOSES. LINE PRESS. TEST PLUG FIGURE 4: GAS VALVE DETAIL MANIFOLD MANIFOLD PRESS.
4. Remove jacket top and insulation from the boiler. 4. Check the bottom head of the boiler and remove Remove the Air Cushion Chamber (ACC) lid and any remnants of the gasket that may be adhering lift out the fan assembly, taking care when to it.
Page 34
1. Turn gas “OFF” at supply (upstream) valve. Turn 4. Remove the boiler from the installation and locate it electrical power to boiler “OFF” at disconnect switch. for further disassembly. Disconnect gas piping and power to boiler. Isolate boiler from hydronic system and drain boiler. 5.
7. Remove the heat exchanger as follows: (3) Lay an approximately 4" piece of the 1/4" Carefully remove the insulation from the top square braided gasket next to and overlapping (front and rear) and sides of the heat the butt joint. Use high temperature silicone exchanger.
3. Assemble Gas Cushion Chamber (GCC) to the Combustion Chamber Inlet. Replace the GCC BACK UP STRIP gasket. Locate clamp ring and secure with 1/4" washers and nuts. GASKET w/ 45° MITER 4. Attach the gas supply tube from the GCC to the gas 1/4"...
8. Remove the Air Cushion Chamber (ACC) 3. Reinstall boiler water, gas and electric connections. Remove the 4-1/4" nuts securing the top lid. Lift off the lid and the spring and set them aside. 4. Thoroughly purge the air from the boiler and system. Lift the fan assembly, disconnect the motor Only after system is purged of air and filled with water leads.
Page 38
6. Apply an anti-sieze compound to the threads of the 12. Mount the electric box and secure it to the jacket with spark plug and screw it into the Combustion the four screws. Chamber. Place bushing over end of wire harness. Inside the electric box: exiting the wire harness 7.
GC-4A "QUICK CHECK" TROUBLESHOOTING GUIDE MPTS-44 ELECTRICAL SYSTEM CHECK FOR BOILERS EQUIPPED WITH THE GC-4A IGNITION CONTROL ON AM SERIES AMBER LIGHT ON FLIP SW. - IT MAY BE OFF BOILER ONLY BOILER ON/OFF SW. CHECK FOR 115V TO BOILER AT TERM. STRIP CHECK FOR 115V TO TERM.
When ordering replacement parts, provide the model and serial number shown on the unit rating plate as well as the part number and name as shown in parts list Parts may be obtained from your local Hydrotherm heating contractor NAME OF PART PART NO.
Page 41
NAME OF PART PART NO. AM-100 AM-150 AM-300 — Gas Cushion Chamber Kit - NG (Has Items 17, 18, 20) BM-7236 Gas Cushion Chamber Kit - NG (Has Items 17, 18, 20) BM-7238 Gas Cushion Chamber Kit - NG (Has Items 17, 18, 20) BM-7240 Gas Cushion Chamber Kit - LP (Has Items 17, 18, 20) BM-7237...
Page 42
NAME OF PART PART NO. AM-100 AM-150 AM-300 Flue Box Gasket Only - Old 3 Hole Style BM-7201 Flue Box Gasket Only - New 3 Hole Style 59-1046 Repl Control Box - NG/LP BM-7128 Repl Control Box - NG/LP BM-7210 Combustion Prove Pressure Switch 02-4851 Bracket Ass’y - Pressure Switch...
Page 43
NAME OF PART PART NO. AM-100 AM-150 AM-300 FOLLOWING COMMON “STREET” PARTS MAY BE AVAILABLE FROM YOUR LOCAL WHOLESALER Hose Clamp 57-4907 Hose Clamp 57-4906 Cross - 1" 56-5101 Cross - 1-1/4" 56-5103 Cross - 1-1/2" 56-5104 Nipple - 1" x 16" LG 53-1206 Nipple - 1-1/4"...
Page 44
JACKET PARTS AND ACCESSORY KITS (Quantity: 1 each) PART NO. NAME OF PART AM-100 AM-150 AM-300 Jacket Top Cover BM-7039 BM-7040 Jacket Upper Panel BM-7260 BM-7263 Jacket Lower Panel BM-7261 BM-7264 Jacket Bottom Cover BM-7144 BM-7048 Jacket Access Panel BM-7262 BM-7265 Jacket Lower Front Panel BM-7166...
Page 45
81/82 FIGURE 9: GENERAL ASSEMBLY MODEL AM-100, AM-150...
Page 46
61/62 FIGURE 10: MODEL AM-100 CONTROL PANEL 61/62 1 2 3 4 5 FIGURE 11: MODEL AM-150 CONTROL PANEL...
Page 47
JACKET ASSEMBLY MODEL AM-300 SIDE PANEL 86/15 BRACKETS 24 83 32 & 33 FIGURE12: GENERAL ASSEMBLY AM-300...
Page 48
260 NORTH ELM STREET 5211 CREEKBANK ROAD WESTFIELD, MA 01085 MISSISSAUGA, ONTARIO L4W 1R3 CANADA (413) 568-9571 • FAX (413) 568-9613 (905) 625-2991 • FAX (905) 625-6610...
Need help?
Do you have a question about the MultiPulse AM Series and is the answer not in the manual?
Questions and answers