Lennox MP03-VDLPM Installation Instructions Manual page 19

Merit plus series direct vent, vented gas fireplace heaters - direct vent models
Table of Contents

Advertisement

TABLE C
H Maximum
V Minimum
(meters)
(meters)
feet
feet
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
**Wall
Firestop/Spacer
Square termination (SV4.5HT-2) shown.
See Table 3 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 30
- Top Vent - ONE 90 DEGREE ELBOW - ELBOW
CONNECTION NOT DIRECTLY AT APPLIANCE
Example: If 20 feet of (H)
horizontal vent run is needed,
then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5
(H) ratio. For every 1 foot of
(V) vertical, you are allowed
5 feet of (H) horizontal run,
up to a maximum horizontal
run of 20 feet.
H
V
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
H
*Wall
Firestop/Spacer
H = 28 inches (711 mm) Maximum
Square termination (SV4.5HT-2) shown.
Figure 31
- Top Vent - ONE 90 DEGREE ELBOW -
CONNECTION DIRECTLY AT APPLIANCE
Support
Bracket
19